Specifications - Marathon Power Track Series User Manual

Line interactive, true sine wave output
Table of Contents

Advertisement

14. Specifications

i
STANDARD RUN-TIME MODELS
GENERAL
Rated Capacity:
Technology:
INPUT
Phase:
Input Voltages:
Input Voltage Range:
Frequency:
AC Frequency Range:
Input Current (120V):
Input Current (230V):
Input Protection:
DC Bus Voltage:
OUTPUT
Output Voltage:
Voltage Regulation:
Voltage Distortion:
Frequency Regulation:
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
Transfer Time:
Efficiency (Standby Mode):
Overload Capacity:
EXTENDED RUN-TIME MODELS
GENERAL
Rated power:
Technology:
INPUT
Phase:
Input Voltages:
Input Voltage Range:
Frequency:
AC Frequency Range:
Input Current (120V):
Input Current (230V):
Input Protection:
DC Bus Voltage:
OUTPUT
Output Voltage:
Voltage Regulation:
Voltage Distortion:
Frequency Regulation:
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
Transfer Time:
Efficiency (Standby Mode):
Overload Capacity:
600VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.6
Line-interactive topology with true sinewave output on battery
Single phase plus ground
110V, 115V, 120V or 220V, 230V, 240V
± 25%
50 / 60 Hz auto sensing
45 - 65 Hz
600VA - 5A, 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A, 3000VA -25A
600VA - 2.6A, 1000VA - 4.4A, 1500VA - 6.5A, 2000VA - 8.7A, 3000VA - 13A
Fuse or circuit breaker for overload and short circuit (model dependent)
600VA - 24V, 1000VA - 24V, 1500VA - 36V, 2000VA - 48V, 3000VA - 96V
110V, 115V, 120V or 220V, 230V, 240V
± 5% (600VA - 3000VA)
< 5% THD with non-linear loads, < 3% THD with linear loads
± 0.5% (while on battery)
or increases by between 9% and 25%
Between 4 and 8 milliseconds including detection time
Greater than 95%
110% for 20 seconds, 125% for 5 seconds
1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.6
Line-interactive topology with true sinewave output on battery
Single phase plus ground
110V, 115V, 120V or 220V, 230V, 240V
± 25%
50 / 60 Hz auto-sensing
45 - 65 Hz
1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A, 3000VA -25A
1000VA - 4.4A, 1500VA - 6.5A, 2000VA - 8.7A, 3000VA - 13A
Fuse or circuit breaker for overload and short circuit (model dependent)
1000VA - 24V, 1500VA - 36V, 2000VA - 48V, 3000VA - 48V
110V, 115V, 120V or 220V, 230V, 240V
± 5% (1000VA - 3000VA)
< 5% THD with non-linear loads, < 3% THD with linear loads
± 0.5% (while on battery)
or increases by between 9% and 25%
Between 4 and 8 milliseconds including detection time
Greater than 95%
110% for 20 seconds, 125% for 5 seconds
19

Advertisement

Table of Contents
loading

Table of Contents