Specifications - Marathon Power vault series User Manual

True on line double conversion
Hide thumbs Also See for vault series:
Table of Contents

Advertisement

9. Specifications

9.1 120V Models
GENERAL
Rated Capacity:
Technology:
INPUT
Phase:
Input Bypass Voltage:
Input Voltage range:
Frequency:
AC Frequency range:
Synchronization range:
Input Current:
Input Power factor:
OUTPUT
Output Voltage:
Voltage regulation:
Voltage distortion:
Frequency regulation
Dynamic response:
Overload capacity:
Efficiency (HE Mode):
Efficiency (On-line Mode):
Crest Factor:
9.2 230V Models
GENERAL
Rated power:
Technology:
INPUT
Phase:
Bypass Voltage:
Input Voltage range:
Frequency:
AC Frequency range:
Synchronization range:
Input Current:
Input Power factor:
OUTPUT
Output Voltage:
Voltage regulation:
Voltage distortion:
Frequency regulation
Dynamic response:
Overload capacity:
Efficiency
Efficiency
Crest Factor:
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.7
True on-line, double conversion topology with integral automatic bypass
Single phase plus ground
96 - 138 VAC (+15% to -20% of 120V nominal - user selectable)
60 / 70 / 80VAC - 144 VAC
(60-144V @ 40% load, 70-144V @ 70% load, 80-144V @ 100% load)
50 / 60 Hz Auto sensing
45 - 65 Hz
± 3Hz
700VA - 7A, 1000VA - 10A, 1500VA - 12A, 2000VA - 16A, 3000 VA - 24A
0.97
100 / 110 / 115 / 120 / 127 VAC (user selectable)
± 2%
< 5% THD with non-linear loads, < 3% THD with linear loads
± 0.25 Hz (while on battery or in free run mode)
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
100 - 125% for 1 min, 125 - 150% for 10 sec
Greater than 95%
Greater than 86%
3 : 1
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.7
True on-line, double conversion topology with integral automatic bypass
Single phase plus ground
184 - 265 VAC (user selectable)
120 / 140 / 160 VAC - 276 VAC
(120V @ 40%, 140V @ 70%, 160V @ 100% load)
50 / 60 Hz Auto-sensing
45 - 65 Hz
± 3Hz
700VA - 4A, 1000VA - 6A, 1500VA - 8A, 2000VA - 10A, 3000VA - 16A
0.97
208 / 220 / 230 / 240 VAC (user selectable)
± 2%
< 5% THD with non-linear loads, < 3% THD with linear loads
± 0.25 Hz (while on battery or in free run mode)
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
100 - 125% for 1 min, 125 - 150% for 10 sec
(HE Mode): Greater than 95%
(On-line Mode): Greater than 86%
3 : 1
28