7DEOH RI &RQWHQWV Saftey Instructions........................2 1.Introduction..........................4 2. System Description.........................4 2.1 General Description.....................4 2.2 System Configuration and Sizing.................5 3. Safety Information........................6 4. Storage.............................6 5. Installation..........................7 5.1 Environment........................7 5.2 AC Power and Load Connections................7 System Wiring Diagram.....................8 120V Front View and Connections..................9 120V Nema Rear View and Connections................10 220V IEC Rear View and Connections................10 Dimensions: 700TR / 1000TR / 1500TR................11...
Page 5
7KH LQVWUXFWLRQV FRQWDLQHG ZLWKLQ WKLV VDIHW\ PDQXDO DUH H[WUHPHO\ LPSRUWDQW DQG VKRXOG EH FORVHO\ IROORZHG DW DOO WLPHV GXULQJ LQVWDOODWLRQ DQG IROORZXS PDLQWHQDQFH RI WKH 836 DQG EDWWHU\ &$87,21 The unit contains dangerous voltage levels. If the UPS is on, but not connected to an AC power supply, the unit’s outlets may still be energized with voltage due to the presence of an additional power source, ie.
1. Introduction The information provided in this manual refers to our ruggedized single phase, 700VA through 1500VA, true on-line uninterruptible power supplies. It covers basic functions, operating and installation instructions, cautionary notes and detail on how to ship, store and handle them. Installation must be carried out in accordance with this manual as well as local electrical regulations and should only be performed by qualified personnel to avoid the risk of electric shock or damage to the unit.
3. Safety Information PLEASE READ THIS SECTION TO AVOID RISK OF SHOCK OR OTHER HAZARDOUS SITUATIONS. 1. Please handle the unit with extreme caution since the batteries contain large amounts of energy. Always store the unit in the orientation marked on the packaging. 2.
7. Batteries & Maintenance DANGER FLUSH EYES HIGH IMMEDIATELY VOLTAGE... WITH WATER. RISK OF SHOCK. SULFURIC DO NOT TOUCH SHIELD EYES ACID UNINSULATED MEDICAL • SPARKS EXPLOSIVE GASES CAN CAUSE TERMINALS OR HELP • FLAMES CAN CAUSE BLINDNESS BLINDNESS OR CONNECTORS.
Procedures Consult User Manual of specific application for additional Safety & Operating requirements. The following safety procedures should be followed during installation: (Always wear safety glasses or face shield.) 1. These batteries are sealed and contain no free electrolyte. Under normal operating conditions, they do not present any acid danger.
Storage 1. Batteries should be stored indoors in a clean, level, dry and cool location. Recommended storage temperature is 0°F to 90°F (– 18°C to 32°C). 2. Stored lead-acid batteries self discharge and must be given a charge six months from date of manufacture to prevent permanent performance degradation.
Cable size selection should be determined by current carrying requirements as well as providing a minimum voltage drop between battery system and operation equipment. Proper techniques should be applied per electrical standards, such as NEC and/or local codes. Note: Excess voltage drop will reduce the support time of the battery system. Temperature The average battery operating temperature should not exceed 95°F (35°C) and should never exceed 105°F (40.5°C) for more than an eight-hour period.
Page 24
1. Conduct a visual inspection of the battery(ies). 2. Record battery and /or string voltage. The accuracy of the DMM (Digital Multimeter) must be 0.05% (on dc scale) or better. The DMM must be calibrated to NIST traceable standards. Because voltage readings are affected by discharge and recharges, for cyclic applications, the battery(ies) must be in a fully charged condition prior to taking readings.
Page 25
APPENDIX B MARATHON POWER BATTERY MAINTENANCE REPORT Inspection Date_______________________________________________________________ No. of Units/String _________________ Company ___________________________________________________________________ Type ____________________________ Address ____________________________________________________________________ Date New ________________________ Battery location and/or number __________________________________________________ Date Installed _____________________ Individual Charger Output ____________________Amp Air Temperature ____________________°F Battery Readings Total Battery String Voltage _______________...
0DLQWHQDQFH As long as all the installation, environmental and operational requirements have been followed and met, the UPS will require little or no maintenance for many years. The batteries are the only component that should eventually need replacing. Their useful life depends primarily on the following two factors;...
Marathon Power warrants to the original purchaser, who must have properly registered the product within 30 days of purchase, and not for the benefit of anyone else that this product at the time of its sale by Marathon Power is free of defects in materials and workmanship for two (2) years from the original purchase date.
Page 32
Marathon Power Inc. 2015 ( WK 6WUHHW +XQWLQJWRQ 3DUN &$ 2IILFH )D[ VXSSRUW#PDUDWKRQSRZHUFRP ZZZPDUDWKRQSRZHUFRP ruggedized vault_user manual 2015 Marathon Power Inc. 2015...
Need help?
Do you have a question about the vault series and is the answer not in the manual?
Questions and answers