Specifications - Marathon Power Sprint Series User Manual

Line-interactive uninterruptible power supply
Table of Contents

Advertisement

13. Specifications

Tower Models
GENERAL
Rated Capacity:
Technology:
INPUT
Phase:
Input Voltages:
Input Voltage Range:
Frequency:
AC Frequency Range:
Input Current (120V):
Input Current (230V):
Input Protection:
DC Bus Voltage:
OUTPUT
Output Voltage:
Voltage Regulation:
Power Factor:
Frequency Regulation:
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
Transfer Time:
Efficiency (Standby Mode):
Overload Capacity:
19" Rack-Mount Models
GENERAL
Rated power:
Technology:
INPUT
Phase:
Input Voltages:
Input Voltage Range:
Frequency:
AC Frequency Range:
Input Current (120V):
Input Current (230V):
Input Protection:
DC Bus Voltage:
OUTPUT
Output Voltage:
Voltage Regulation:
Power Factor:
Frequency Regulation:
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
Transfer Time:
Efficiency (Standby Mode):
Overload Capacity:
425VA, 525 VA, 625 VA, 800VA, 1000 VA, 1200 VA, 1500VA, 2200VA
Line-interactive topology with simulated sinewave output on battery
Single phase plus ground
110V, 115V, 120V or 220V, 230V, 240V
± 25%
50 / 60 Hz auto sensing
45 - 65 Hz
425-3.5A, 525-4.4A, 625-5.2A, 800-6.7A, 1000-8.3A, 1200-10A, 1500-12.5A, 2200-18.3A
425-1.8A, 525-2.3A, 625-2.7A, 800-3.5A, 1000-4.3A, 1200-5.2A, 1500-6.5A, 2200-9.6A
Fuse or circuit breaker for overload and short circuit (model dependent)
425VA ~ 625VA - 12V, 800VA ~ 1500VA - 24V, 2200VA - 48V
110V, 115V, 120V or 220V, 230V, 240V
± 5% (425VA - 2200VA)
0.6
± 1% (while on battery)
or increases by between 9% and 25%
Between 2 and 4 milliseconds including detection time
Greater than 95%
110% for 60 seconds, 130% for 3 seconds
1000 VA, 1500 VA, 2200 VA
Line-interactive topology with simulated sinewave output on battery
Single phase plus ground
110V, 115V, 120V or 220V, 230V, 240V
± 25%
50 / 60 Hz auto-sensing
45 - 65 Hz
1000VA - 8.3A, 1500VA - 12.5A, 2200VA - 18.3A
1000VA - 4.3A, 1500VA - 6.5A, 2200VA - 9.6A
Fuse or circuit breaker for overload and short circuit (model dependent)
1000VA - 18V, 1500VA - 24V, 2200VA - 48V
110V, 115V, 120V or 220V, 230V, 240V
± 5% (1000VA - 2200VA)
0.6
± 1% (while on battery)
or increases by between 9% and 25%
Between 4 and 8 milliseconds including detection time
Greater than 95%
110% for 60 seconds, 130% for 3 seconds
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents