Note : Before breaking into the gas supply a pressure drop test should be
carried out to establish that the existing pipework is sound.
b)
Before making the final gas connection, thoroughly purge the gas
supply pipework to remove all foreign matter, otherwise serious
damage may be caused to the gas control valve on the fire.
Failure to purge the gas supply will invalidate the guarantee.
c)
The gas connection should be made to the appliance inlet elbow to
using 8mm rigid tubing.
d)
Remove the pressure test point screw from the inlet elbow and fit a
manometer.
e)
Turn on the main gas supply and carry out a gas tightness test.
f)
To light the appliance, refer to section 3.2 on pages 15 to 17.
NOTE : Please ensure that the battery that has been disconnected at the factory prior
to packing is re-connected. The battery is located at the bottom L/H/S of the
combustion chamber, attach the flying lead to it
g)
Check that the gas pressure is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w.g.)
h)
Turn off the fire, remove the manometer and refit the pressure test point
screw. Check the pressure test point screw for gas tightness with the
appliance turned on using a suitable leak detection fluid or detector.
2.6

SECURING OF THE COMBUSTION CHAMBER TO THE WALL

a)
The combustion chamber should be secured to the wall using the
4 off screws and rawlplugs provided. Drill 4 off 6.0mm diameter holes
into the wall behind the product as shown below in Fig. 8
Fig. 8
6 inch / 150mm core
drilled hole to suit
the flue pipes at
420mm height
Supplied By www.heating spares.co Tel. 0161 620 6677
495mm
Dimensions from top
75mm
face of the hearth
463mm
panel to centre of
mounting holes
11