ATTACK DP STANDARD Instructions For Use Manual page 11

Wood gasifying boiler
Table of Contents

Advertisement

Actual value of this setting can be also checked in the temperature display mode.
If the flue gas temperature is in the operation mode after burning-up lower than the value set by
the button of additional thermostat, then the suction fan and the circuiting pump are blocked,
which is signalized by flickering of additional thermostat´s control light. In this case it is
necessary to decrease the adjusted flue gas temperature value by the button of additional
thermostat, until the control light stops to flicker. Consequently it comes to restart of the
suction fan and circuiting pup operation.
When the fuel is being burned-down and the flue gas temperature decreases under the value set
by flue gas thermostat, the boiler is switched into the fuel shortage control mode and after
expiration of the set time – parameter [Fb30] – it comes to automatic boiler stop.
It is necessary to make setting of the boiler stop at flue burn-down adequately to flue gas
temperature, when the boiler is started-up and then to check it from time-to-time.
After pressing the START button, ventilator starts to work and the control process begins.
Ventilator is stopped by the STOP button.
If the regulator is not in the operation mode, temperature of water in the boiler is indicated on
display.
Example: [70°C] - STOP mode
[70°C] - Operation mode
[70°C] - Fire keeping in operation mode
Manual start of ventilator
During the boiler operation might the user need to turn the fan on manually (e.g. for suction of
gas from boiler before and during fuel load). After pressing and holding of START button for 3
seconds, the ventilator starts. Ventilator will work for period set in service mode or until the
STOP button is pressed.
Temperature display mode
To enter into the temperature display mode, press the OK button. Enter into this mode will be
indicated by quick flickering of the additional thermostat´s control light. Use buttons < and >
to browse in the information displayed to different temperatures. To exit the temperature
display mode, select [END] and press the OK button or wait for 1 min.
List of temperatures, which are disposable in the temperature display mode:
Indication
C 80
Required boiler temperature
C
100
Temperature set by the additional thermostat's button (flue gas / room)
180°
Actual temperature of additional thermostat (flue gas / room)
End
Exit from menu of the temperature display
Parameter
10