Zennio InZennio Z38i Product Manual

Zennio InZennio Z38i Product Manual

Touch panel knx
Hide thumbs Also See for InZennio Z38i:

Advertisement

Quick Links

InZennio Z38i
KNX Touch Panel
ZN1VI-TP38i
Program version: 2.2
Manual edition: a

Advertisement

Table of Contents
loading

Summary of Contents for Zennio InZennio Z38i

  • Page 1 InZennio Z38i KNX Touch Panel ZN1VI-TP38i Program version: 2.2 Manual edition: a...
  • Page 2: Table Of Contents

    INDEX Document updates ............................3 Introduction ............................4 1.1. InZennio Z38i........................... 4 1.2. Installation ............................5 Configuration ............................7 2.1. Product ............................7 2.2. Control using IR remote ........................9 ETS Parameterization ..........................10 3.1. Default configuration ........................10 3.2.
  • Page 3: Document Updates

    Reorganization of the information in Section 1 into two independent sections: 1. Introduction and 2. Configuration More information in section 1.2. Installation 2.2a Version 1.1 of Building Thermostat has been integrated New format of the product manuals ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 4: Introduction

    1. INTRODUCTION 1.1. INZENNIO Z38I InZennio Z38i is an LCD Touch Panel with Room Thermostat, Binary Inputs and IR Receiver built-in. Z38i is a great solution for demanding applications in hotel rooms, apartments, offices, and in any room where it is necessary to manage climate, shutters, lights, scenes, etc.
  • Page 5: Installation

    4 binary inputs for the connection of push buttons or switches/sensors. Control through an IR remote control 1.2. INSTALLATION In the figure 1.2, the connection scheme of InZennio Z38i is shown: 1.- KNX connector 2.- Programming button 3.- Programming LED 4.- Inputs connection...
  • Page 6 Figure 1.3. Z38i calibration To obtain more detailed information about the technical features of InZennio Z38i, as well as security and installation information, please read the controller Datasheet, included in the original package of the device and also available at: http://www.zennio.com.
  • Page 7: Configuration

    2. CONFIGURATION 2.1. PRODUCT The panel InZennio Z38i allows controlling a set of functionalities in a domotic installation in a simple and intuitive way. There are a set of parameters that refer to the general working of the panel, such as: lighting, header configuration, internal temperature sensor, password, etc.
  • Page 8 Z38i allows enabling and configuring in an independent way the functionality of up to 2 thermostats, with the "Building" functionality. The working and ETS configuration of this kind of thermostat is detailed in the specific documentation "Zennio Building Thermostat", available at: http://www.zennio.com.
  • Page 9: Control Using Ir Remote

    Home or Home 2 of Z38i, according to the parameterization (see section 3.2. Remote control). Buttons arrangement on the remote controller is similar to the Home and Home 2 boxes structure to make its control easier. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 10: Ets Parameterization

    For starting to parameterize the Z38i touch panel it is necessary, once the ETS program has been opened, importing the data base of the product (version 2.2 of the application program InZennio Z38i). Next, the device is added to the project where desired. Click the right mouse button on the device and select "Edit parameters"...
  • Page 11 Inputs: to enable and configure individually each input of the controller. Thermostats: to enable and configure individually each thermostat of the controller. In the following sections, all the aforementioned windows are explained in detail. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 12: General

    KNX bus that have the reading flag "R". Moreover, this functionality allows establishing a delay for sending the initial values since the power is recovered (to get an immediate sending, set 0 in the field "Delay"). ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 13 Remote control: This parameter allows enabling the zones of the remote controller and associate each of them to either any of both Home or Home 2 pages, to control them remotely. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 14 Password: With this option, it will be possible to configure a customizable password, by establishing 4 digits from 0 to 9, which must be written to access those pages on which security was enabled. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 15 2.- After introducing it correctly, the word “NEW” will appear. That is the moment to insert the new password. 3 - "REPEAT". Insert again the desired new password. The left arrow button allows deleting/cancelling, in case of wrong-typing the digits. Figure 3.8. Password changing from the panel ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 16: Pages

    Every enabled page has some parametrizable fields: Name: This field allow users to associate a name to any of the InZennio Z38i pages; this name will appear on any of the page headers the user is moving through (12 free characters are available to set the name).
  • Page 17: Home And Home

    Note: Home Page will be shown again 90 seconds after last interaction on the display took place. The field "Security" only appears for Home 2 page. The Home page is enabled by default. Access to the Home page cannot be restricted. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 18 1 is pressed (short or long press).  1: sending of the value "1" to the KNX bus through the corresponding object every time the button 1 is pressed (short or long press). ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 19 ON/OFF: This is the most basic control type. It can be selected an indicator to show the ON/OFF light status.  On/Off + Simple Regulation (4 bits): It is possible to simulate a common switch action, turn On/Off (short press on the buttons), or a discreet regulation (long press ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 20 "[Home x; Box y] Stop shutter", it will be possible to raise/lower shutters and even knowing its exact position at any time (if the corresponding indicator is enabled). There will be two buttons in the box, one for lowering/stopping the shutter and other for rising/stopping it. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 21 This can be very useful if there are free boxes in “Home” or “Home II” pages because that way, the user will avoid browsing between the different pages and will have access directly to determinate specific functions. It is possible to access to this (depending on the configuration applied to the function): ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 22 (Short press: raise or lower one single point in the range with every short key press; Long press: raise or lower 10 points in the range with every long key press). ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 23 Icon: An icon can be associated to the page box.  Scenes Example: Guess the “Scene Night” is defined (programming the Panel with parameters and group addresses via ETS):  Turn all the lights Off  Turn Off the Heating and the A/C Systems ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 24 Climate Control.  Control type: To select between Absolute Temperature (default range [10ºC, 30ºC] and associated objects “Temperature Control” and “Temperature indicator”) or Temperature Offset (default range [-10ºC, 10ºC], and the same associated objects). ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 25 1 byte indicator: One byte provides much more information relating to an event than one bit. This indicator is normally used with percentages (%) relating to particular events (shutter position, wind speed…), however another possible configuration option is a numerical range among 0 and 255. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 26 Security control: In the same way that it exists the possibility to protect any page (see section 3.2. Password) against non-authorized access; this protection is also available for the boxes individually in “Home” and “Home 2”. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 27 KNX installation, such as light or shutter controllers. This object must be linked to the same group address as the corresponding control objects, in charge of switching on/off the devices of the installation implied in the presence simulation. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 28: Specific

    Next, all of them are explained in detail. Scenes Two pages are available (“HOME” and “HOME 2”) where there is the possibility to configure one or several boxes to scenes control. Figure 3.12. Specific page: Scenes ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 29  Function Select element: Hours Minutes  Sent value (On/Off) Function Modify the Weekdays selected element: Increase the Hour/Minute Change the sent value/s (On/Off) Check/Uncheck Weekdays Figure 3.14. Timer page with its 4 boxes configured ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 30 - Box 2 Linked to scene number 64. Only for ON  - Box 3 Linked to scene number 1. Only for OFF  - Box 4 Linked to scene number 52. Only for ON ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 31 It is possible to control the two internal thermostats of the panel through these specific Climate pages. For this aim, it is necessary to properly link, via group addresses, the communication objects of the Climate page with the objects associated to the different thermostat options. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 32 (11 free characters are available to set the name).  Icon: A pair of icons can be associated to the page box. The parameterization of the 6 different boxes in the specific climate page is detailed next: ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 33 This setpoint value can be established in two different ways:  Float-point object: the desired setpoint temperature can be controlled in two different ways (“Control Type”), but always through a 2-bytes communication object 2 “[Clima x] Setpoint Sending”: ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 34 Depending on the selected option, one of these pairs of communication objects will be enabled:  For the Cool/Heat configuration: the 1-bit objects “[Clima x] Mode Sending” and “[Clima x] Mode Reception”. Via the object “Mode Sending”, the value of the current ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 35 (see Annex II.  BOX 5 (Special Modes): When enabling this box, it will be possible to switch from one special climate mode to another: Comfort, Standby and Economic and it may be ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 36: Page Technical Alarms

    This is a specific screen, with up to six independent boxes in charge to monitor the bus looking for possible warning conditions in the KNX installation (gas, smoke...). The Touch Panel InZennio Z38i can be configured to warn the user in case of incidents inside or outside of the room where the display is installed.
  • Page 37 Once the warning reception is confirmed by the user (pressing the OK button), the screen will recover its normal state. After 90 seconds, InZennio Z38i display will show again the “Home” default screen. It is Really Important to know that confirming a warning does not make the Danger icon disappear from the box affected;...
  • Page 38: Configuration Page

    Time (together with the room temperature) is always displayed in the middle upper section of the display.  When setting the time, the display will send the new settings to the bus through its own Communication Objects. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 39 Note II: Take into account that after the reset a few seconds delay could take place respecting correct time; whereas after a bus failure this delay can be much bigger (it depends on the duration of the bus failure). This is the aspect the configuration page shows: ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 40: Inputs

    Depending on the “Threshold Time” it can be distinguished two different actions: Short press or Long press. Typical key press devices, as keyboards, are used to be configured as push button inputs. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 41 Block: This parameter uses the object "[Ix] Block". This object will disable/enable the corresponding input. When receiving the value “1” through this object, the InZennio Z38i will ignore any pulsation on the input. When receiving the value "0", the input is enabled again.
  • Page 42: A) Short Press

    "0" and "1" alternately through the object "[Ix][Short Press] Stop/Step Shutter (switched)". ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 43 "[General] Scenes" to the bus; a scene on the bus may be managed with the input through this Object.  Response: Choose whether the scene will be “Run” or “Saved”.  Scene: This parameter identifies the scene to Run/Save with the corresponding Input. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 44: B) Long Press

    Falling edge: select the sending value when this edge happens: Nothing, 0, 1 or switching. Sending of "0" Delay: specify the time, in seconds, after which the value "0" will be sent, once received the corresponding order. ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 45: Thermostats

    (value between 0 and 255, in seconds). 3.5. THERMOSTATS InZennio Z38i application offers the possibility to enable and configure up to 2 thermsotats, independently. Figure 3.18. Thermostat 1 Configuration To obtain theoretical information about the Zennio thermostat functioning, as well as information about its ETS configuration, please consult the specific documentation "Thermostat Zennio"...
  • Page 46: Annex I. Communication Objects

    [Home x Box x] Stop shutter 0 or 1 -> Stop 1 bit Indifferent Indifferent [Home x Box x] Presence simulation 0=Disabled; 1=Enabled 42-53 4bits Indifferent Indifferent [Home x Box x] Light dimming 4-bits dimmer control ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 47 [Clima x] On/Off reception 130-133 1 byte [Clima x] Fan reception 0%=Auto; 1-33%: Minimum; 34-66%: Medium; >67%: Maximum [Clima x] Fan reception 0=Auto; 1=Minimum; 2=Medium; 3=Maximum 134-137 1 bit [Clima x] 1 bit reception 0=Off; 1=On ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 48 [Ix] [Long Press] Darker Lg.Pr.->Dark; Lg.Pr->Stop [Ix] [Long Press] Brighter/Darker Lgh.Pr->Bright/Dark;Lg.Pr->Stop [Ix] [Long Press] Move Down Shutter Long Pr. -> Sending of 1 (Down) [Ix] [Long Press] Move Up Shutter Long Pr. -> Sending of 0 (Up) ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 49 1 byte 0-100% Last [Tx] Control variable (Heat) PI control (Continuous) 236.238 1 bit Last [Tx] Additional Cool Temp > (Setpoint+Band) => "1" 237.239 1 bit Last [Tx] Additional Heat Temp < (Setpoint-Band) => "1" ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com...
  • Page 50 BECOME USER! http://zennioenglish.zendesk.com TECHNICAL SUPPORT...