Toshiba RAV-SM564UTP-E Service Manual page 68

Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

DN
Item
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
Louver type
19
(Adjustment of air direction)
In automatic cooling/heating, temp.
width of cool → heat, heat →
1E
cool mode selection control point
28
Automatic reset of power failure
2A
Selection of option / error input (CN70)
Selection of thermostat output
2b
(T10
)
2E
Selection of HA (T10) terminal
31
Vent fan (Single operation)
32
Sensor selection
High ceiling selection
5d
(Air volume selection)
60
Timer setting (Wired remote controller)
SVM-13010_051-106.indd 68
SVM-13010_051-106.indd 68
Function selection CODE No. (DN) list
Contents
0
0
0
: 0
N
o
n
e
0
0
0002: 2500H
0003: 5000H
0004: 10000H
0005: Clogging sensor used
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
to
0064: No.64 unit
0099: Undecided
0000: No shift
0001: +1°C
0002: +2°C
to
0010: +10°C
(Up to +6 is recommended.)
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0000: (1-way cassette)
0001: (4-way cassette) to 0037
0000: Undecided
0001 to 0034
0001: No.1 unit
to
0030: No.30 unit
0001: No.1 unit
to
0064: No.64 unit
0000: Individual
0001: Master unit in group
0002: Follower unit in group
0000: No louver model
0001: Swing only
(0002:1-way)
(0003:2-way)
0004: 4-way
0000: 0 deg
to
0010: 10 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0
0
0
: 0
N
o
n
e
0
0
0000: Filter input
0001: Alarm input
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0001: Card input
0002: Fire alarm input
(Forgotten to be off)
0000: Impossible
0001: Possible
0000: Body TA sensor
0001: Remote controller sensor
0000: Operable
0001: Operation prohibited
– 68 –
FILE NO. SVM-13010
At shipment from factory
0
: 1
1
5
0
H
According to type
0000: Standard
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
According to model type
0003: 3 deg
0
: 1
r P
v o
d i
e
d
0000: None
0002: Humidifier
(Air cleaner, etc.)
0000: Thermostat ON
0000: Normal
0000: Impossible
0000: Body sensor
0000: Standard
0000: Operable
(Ts±1.5)