[L20 error]
Are wiring connections
to communication lines
U3 and U4 normal?
YES
Is not the multiple same central
control system addresses connected?
NO
Check central controller
(including network adapter) and
indoor P.C. board (MCC-1570).
Defect → Replace
[L30 error]
Are outside devices of
connector CN80 connected?
YES
Do outside devices normally work?
YES
Check cause of operation.
[P30 error] (Central controller)
Is group operation carried out?
YES
Is there check code
on follower unit in main
and sub remote controllers?
YES
Check corresponding
indoor unit/outdoor unit.
SVM-13010_051-106.indd 51
SVM-13010_051-106.indd 51
NO
YES
Correct central control system address.
NO
Check indoor P.C. board (MCC-1570).
NO
NO
NO
Check indoor P.C. board (MCC-1570).
– 51 –
FILE NO. SVM-13010
Correct wiring connection.
Defect → Replace
Check outside devices.
Defect → Replace
Defect → Replace