Toshiba RAV-SM564UTP-E Service Manual page 29

Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

No.
Item
6
Air speed
selection
(Continued):
SVM-13010_001-050.indd 29
SVM-13010_001-050.indd 29
Outline of specifications
Standard
CODE No.
[5d]
0
SW501 (1)/(2)
OFF/OFF
Tap
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
F1
F2
HH
F3
F4
H+
F5
HH
F6
HH
F7
H+
H+
F8
H
F9
H
L+
FA
L+
FB
L+
L
FC
L
FD
UL
SM56
SM80
Tap
Revolution speed (rpm)
F1
610
630
F2
550
590
F3
500
530
F4
450
470
F5
400
450
F6
390
440
F7
370
410
F8
350
380
F9
340
370
FA
330
350
FB
320
330
FC
310
320
FD
250
250
3) In heating operation, the mode changes to [UL] if thermostat
is turned off.
4) If Ta ≥ 25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after Tc
entered in E zone of cool air discharge preventive control
(Item 7).
5) In automatic cooling/heating operation, the revolution
frequency of (HH) is set larger than that in the standard
cooling/heating operation.
F5
F4
Tc
(˚C)
Tcj
47
42
F5
6) Self-clean operation
When performing self-clean operation after stopping the
cooling operation, the mode becomes [UL] (210 rpm).
– 29 –
Type 1
Type 3
Type 6
1
3
6
ON/OFF
OFF/ON
ON/ON
HH
HH
HH
HH
H+, H H+, H
H+
H+, H H+, H
L+, L
L+, L
H
H
L+
L+
L
L
L+
L
L
UL
UL
SM110
SM140
SM160
700
700
700
670
670
670
660
660
660
640
650
650
620
640
640
610
630
630
550
560
580
490
490
530
480
480
520
450
460
490
400
430
450
400
420
440
300
300
300
However the revolution
frequency is restricted in the
automatic heating operation as
shown in the following figure.
FILE NO. SVM-13010
Remarks
Selection of high
ceiling type
CODE No.:
[5d] or selection of
HH
high ceiling on P .C.
board SW501
UL
Tcj:
Indoor heat exchanger
sensor temperature
However only when
the high ceiling
selection is set to
[Standard]
[Self-clean
] is
displayed.
2/1/13 10:59 AM
2/1/13 10:59 AM