5-2. Control Specifications
No.
Item
1
When power
supply is reset
2
Operation
mode selection
3
Room temp.
control
SVM-13010_001-050.indd 26
SVM-13010_001-050.indd 26
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are distin-
guished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
Remote controller
command
STOP
Air conditioner stops.
FAN
Fan operation
COOL
Cooling operation
DRY
Dry operation
HEAT
Heating operation
AUTO
• COOL/HEAT operation mode is
automatically selected by Ta, Ts
and To for operation.
• The operation is performed as
shown in the following figure
according to Ta value at the first
time only. (In the range of Ts +
α
–1 < Ta < Ts +
thermo. OFF (Fan)/Setup air
volume operation continues.)
+1.0
Cooling thermo. OFF (Fan only)
Ta
α
• Setup air volume
Ts +
(˚C)
-1.0
α
is corrected according to the outside temperature.
Outside temp.
No To
To ≥ 24°C
24 > To ≥ 18°C
To < 18°C
To error
1) Adjustment range: Remote controller setup temperature (°C)
COOL/DRY
Wired type
18 to 29
Wireless type
17 to 30
Control outline
α
+ 1, Cooling
Cooling
operation
Heating
operation
α α α α α
Correction value (
)
0K
–1K
0K
+1K
0K
HEAT
AUTO
18 to 29
18 to 29
17 to 30
17 to 30
– 26 –
FILE NO. SVM-13010
Remarks
Air speed (rpm)/
Air direction adjustment
Ta: Room temp.
Ts: Setup temp.
To: Outside temp.
k = deg
2/1/13 10:59 AM
2/1/13 10:59 AM