How To Use Drain Pump Kit Of Option - Toshiba RAS-18UFHP-E3 Service Manual

Air-conditioner under ceiling / console type
Table of Contents

Advertisement

2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is not
indicated on the display even if the selector switch
is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
A
B
PRESET
START/STOP
AUTO
FAN
MODE
SWING
ECO
Hi-POWER
TIMER
FIX
MEMO
ON
OFF
SET
CLR
FILTER
RESET
CLOCK CHECK
Fig. 8-6-3
3. Confirm that the indoor unit can operate with the
new setting.

8-7. How to Use Drain Pump Kit of Option

In the case of upward drainage from the unit (Under
ceiling installation). It is necessary to use Drain pump
kit of option parts. By using a Drain pump kit, it
becomes possible to raise 300 mm from a ceiling side.
Please follow the installation manual of Drain pump kit
(TCB-DP10CE) attachment.
A
B
[MODE] button
[CHECK] button
– 54 –
FILE NO. SVM-04032
300 mm
Drain pump kit
Fig. 8-7-1