Toshiba RAS-18UFHP-E3 Service Manual page 28

Air-conditioner under ceiling / console type
Table of Contents

Advertisement

5-6. RAS-24UFP-E3 / RAS-24UA-E3
RAS-24UFPX3 / RAS-24UAX3
RAS-24UFPX3-T / RAS-24UAX3-T
0.39m
(Connecting pipe)
∅15.88 mm
0.39m
(Flexible pipe)
∅15.88 mm
O.D.:15.88 mm
Packed valve
(∅15.88 )
Compressor
2JS386D5BB02
50Hz
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.
Multi blade fan
P
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
0.4
0.7
0.3
T
Indoor unit
Evaporator
Mark (
) means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
11.0
12.0
1.0
– 27 –
FILE NO. SVM-04032
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅2.0x650S
Dryer
Refrigerant
R-22 1.80kg
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
High
27/19
High
32/23
Low
21/15
Outdoor
35/24
43/26
21/15

Advertisement