Toshiba RAS-18UFHP-E3 Service Manual page 29

Air-conditioner under ceiling / console type
Table of Contents

Advertisement

5-7. RAS-24UFP-AR3 / RAS-24UA-AR3
0.39m
(Connecting pipe)
∅15.88 mm
0.39m
(Flexible pipe)
P
∅15.88 mm
O.D.:15.88 mm
Packed valve
(∅15.88 )
Accumulator
Compressor
2JS386D5BB02
50Hz
Standard
Cooling
High temperature
Low temperature
* SASO Standard's condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Indoor unit
Evaporator
Multi blade fan
Condenser
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
exchanger interchanging
pressure P
pipe T (°C)
(MPaG)
0.4
0.7
0.3
– 28 –
FILE NO. SVM-04032
T
Packed valve
(∅6.35)
Capillary tube
∅2.4x1400S
Dryer
Refrigerant
R-22 1.63kg
Mark (
) means check points of Gas Leak
Fan speed
(indoor)
11.0
High
12.0
High
1.0
Low
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
27/19
35/24
32/23
52/31*
21/15
21/15

Advertisement

Table of Contents
loading

Table of Contents