Toshiba RAS-18UFHP-E3 Service Manual page 23

Air-conditioner under ceiling / console type
Table of Contents

Advertisement

5-1. RAS-18UFHP-E3 / RAS-18UAH-E3
Cooling
0.39m
Heating
(Connecting pipe)
∅12.70 mm
0.39m
(Flexible pipe)
∅12.70 mm
O.D.:12.70 mm
Packed valve
(∅12.70)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50Hz
Standard
Heating
High temperature*1
Low temperature
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
5. REFRIGERATION CYCLE DIAGRAM
Multi blade fan
P
Muffler
PH250X3-4LM
Accumulator
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
0.4
0.5 ~ 0.6
0.3
0.4
0.5
0.3
T
Indoor unit
Evaporator
Capillary tube
∅0.8x500S
Capillary tube
∅2.0x1200S
Mark (
) means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
45.0
49.0 ~ 58.0
34.0
10.0
15.0
1.0
– 22 –
FILE NO. SVM-04032
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅1.2x1500S
Refrigerant
R-22 1.29kg
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
High
20/–
Low
27/–
High
20/–
High
27/19
High
32/23
Low
21/15
Outdoor
7/6
24/18
–10/–10
35/24
43/26
21/15