4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No.
Parts name
1
Fan motor (for indoor)
2
Thermo sensor (TA-sensor)
3
DC-DC transformer (T01)
4
Microcomputer
Heat exchanger sensor
5
(TC-sensor)
6
Line filter (L01)
7
Diode (DB01)
8
Capacitor (C02)
9
Fuse (F01)
10
Varistor (R21, R22)
11
Resistor (R01)
12
Louver motor
4-2. Outdoor Unit (RAS-18UAH-E3)
No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve)
6
Thermo sensor
7
Magnetic contactor
8
Transformer
9
Microcontroller
10
Varistor (R73, R74, R86)
11
Fuse (F01)
Type
AFP-220-50-4A
———
SWT-47
TMP87CM40AN
———
SS11V-R07190
D3SBA60
KMH400VSSN47M22S
TSCR
15G561K
RF-2TK5R6
MP35EA12
Type
Output (Rated) 1500 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
PH250X3-4LM
Winding resistance (Ω)
(at 20°C)
Output (Rated) 65 W, 6 poles, 1 phase, 220 – 240 V, 50 Hz
KFG6-71SB5P-T3 Winding resistance (Ω)
(at 20°C)
451205KQ
AC 450 V, 2µF
371456JCR
AC 370 V, 45µF
VHV (STF)
AC 220 – 240 V
TE / TD
10 kΩ at 25°C / 50 kΩ at 25°C
220 − 240 V, 50 Hz
CLK-26J
TT-05
220 – 240 V
TMP47C840N
15G471K
470 V
MT3
T6.3 A, 250 V
– 18 –
FILE NO. SVM-04032
Specifications
Output (Rated) 50W, 220 − 240V
10kΩ at 25°C
DC 390V, Secondary DC 12V, 7V
10kΩ at 25°C
19mH, AC0.7A
4A, 600V
47µF, 400V
T6.3A, 250V
560V
5.6Ω, 2W
Output (Rated) 2W, 6poles, 4phase,
DC 12V
Specifications
C-R
2.29
Red-Black
64.4
C-S
1.22
White-Black
127.4