Toshiba RAS-18UFHP-E3 Service Manual page 27

Air-conditioner under ceiling / console type
Table of Contents

Advertisement

5-5. RAS-24UFHP-E3 / RAS-24UAH-E3
Cooling
0.39m
Heating
(Connecting pipe)
∅15.88 mm
0.39m
(Flexible pipe)
∅15.88 mm
O.D.:15.88 mm
Packed valve
(∅15.88)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50Hz
Standard
Heating
High temperature*1
Low temperature
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Indoor unit
Multi blade fan
P
PH310X3-4MM
Accumulator
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
0.4
0.5 ~ 0.7
0.3
0.4
0.5
0.3
T
Evaporator
Capillary tube
∅0.8x500S
Mark (
) means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
43.0
52.0 ~ 59.0
36.0
11.0
12.0
1.0
– 26 –
FILE NO. SVM-04032
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅2.4x1400S
Refrigerant
R-22 1.63kg
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
High
20/–
Low
27/–
High
20/–
High
27/19
High
32/23
Low
21/15
Outdoor
7/6
24/18
–10/–10
35/24
43/26
21/15

Advertisement

Table of Contents
loading

Table of Contents