Editing Outputs - Mace HydroMace 3000 Product Manual

Weatherproof monitoring and telemetry platform for remote locations mace hydromace 3000
Table of Contents

Advertisement

22.1 adding outputs
Continued
-
3. Select the "Channel" from the drop down
list that you wish to output. In this example the
channel named "Flow Rate" will be output from
"I/O Module @ 2" on "4..20mA output #1". Click
"Continue" to complete adding the new output.
The "Configure outputs" dialogue box will re-
appear with the new output listed.
NOte: Only channels that are suitable for outputting as a 4-20ma
proportional current will be available for selection
22.1.2 Adding a pulse output
1. From the "Select output type" dialogue box highlight
"Pulse out" and click "Continue". The "Select output"
dialogue box will appear.
2. Select the "Digital output #X" that you wish to use
and click "Continue". The "Select source channel"
dialogue box will appear.
3. Select the "Channel" from the drop down
list that you wish to output. In this example
the channel named "Total" will be output from
"I/O Module @ 2" on "Digital output #1". Click
"Continue" to add the new output. The "Configure
outputs" dialogue box will re-appear with the new output listed.
NOte: Only channels that are suitable for "pulse" outputting will be
available for selection
72
SeCtion b SoFtware Manual

22.2 editing outputs

WarNINg: all configured output channels MUSt
be edited prior to starting the hM 3000. editing
the channel/s enables the correct configuration
information to be sent to the controller module.
From the "HM 3000 Settings" dialogue box click "Configure outputs" and the
"Configure outputs" dialogue box will appear.
1. Highlight the channel you wish to edit and click "Edit". An output specific
"Edit output" dialogue box will appear.
2. Edit the settings to suit your application in the "Edit... output" dialogue
boxes as per the recommendations found on the following page. Click
"Apply" to save the settings then click "Exit" to return to the "Configure
outputs" dialogue box.
Removal of outputs
From the "Configure outputs" dialogue box highlight the "Output" you wish
to remove and click "Remove". You will be prompted to confirm the removal.
RetuRn to toC
RetuRn to toC
MaCe HydRoMaCe 3000 Product Manual
73