Removal Of Refrigeration Cycle Components - Movincool OFFICE PRO 36 Service Manual

Hide thumbs Also See for OFFICE PRO 36:
Table of Contents

Advertisement

Repair Section
54

9.2 Removal of Refrigeration Cycle Components

CAUTION
• Before any refrigeration cycle component can be replaced, it is necessary to recover the
refrigerant using standard recovery procedures and equipment.
• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal (1 L/min)) through the
pinch-off tube during any brazing operation.
• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,
to protect them from the flame.
• Evaporator
• Capillary tube
• Condenser
• Compressor
• High Pressure Switch
< NOTE >
When replacement of the compressor, attach the two pipes (Pipe 1, Pipe 2) which are packaged
in Compressor Assy as following figure.
B
A
Pipe 1
Pipe 2
E
C
F
D
Part to Replace
Disconnect At
Compressor
A & F
Condenser
A & B
Capillary Tube
C & D
Evaporator
C & E
I001811