Display
Cause
F1
Parameter in memory not found
F2
Internal Operations error
F3
Internal memory parameter error
F4
Internal memory error
F5
Analog test fail
F6
Gas type parameter error
E7
Appliance parameter not defined
F0
Burner Control routine state error
E5
Burner Control error
E6
Burner Control routine check sum error
F8
Fan stopping error
F9
Gas Control error
F7
Ionization error at standby.
FA
Gas leakage error, gas valve circuit not
closing properly.
Table 54
* By installer or service technician only.
Greentherm
Solution
1. Replace ECU (Electronic Control Unit) if there are repeated errors.
1. Check primary fan cable harness
2. Check fan rotation in standby
3. Check proper function of primary fan
4. Replace ECU (Electronic Control Unit)
1. Check Gas Valve cable harness (connection to gas valve and to ECU)
2. Check Gas Valve (Replace if necessary)
3. Replace ECU (Electronic Control Unit)
1. Loose connection to the flame ionization rod. Verify that the thinner wire leading from the
control unit is securely connected to the set of electrodes located on the lower front of the
heat exchanger.
2. Flame ionization rod or control unit may be damaged. Contact Bosch Water Heating for
further instruction.
1. Disconnect power supply cord and check wire connections on gas valve and the two
connectors on the control board.
2. Flow water out of a hot water tap above the minimum activation point of 0.5 GPM.
Measure voltage at the gas valve wire plug connection. The voltage should measure 24VDC
between the left pair of wires and 24VDC between the right pair of wires when the unit is
operating. If voltage is not proper, contact Bosch Water Heating for further instruction.
3. Gas valve may be defective, contact Bosch Water Heating for further instruction.
Problem solving | 53