Site Requirements - Vent-Axia HR25 Solo LH Installation And User Instruction Manual

“through the wall” heat recovery ventilator
Hide thumbs Also See for HR25 Solo LH:

Advertisement

Fig.2
Ceiling
300mm minimum
Fig.3
© Copyright abc 2006
50mm minimum
50mm minimum
125mm minimum
300mm minimum

2.0 Site Requirements

2.1 Information
1. The unit is designed for installation in
external walls with a thickness of up to 310mm.
For wall thicknesses above 310mm, the 'L'
version of the appropriate model must be used
(see page 12 ). The 'L' models are suitable for wall
thicknesses up to 425mm.
2. The unit must be sited and connected by a
suitably competent person and be in
accordance with current U.K. Building
Regulations and I.E.E. Wiring Regulations (BS
7671).
3. The unit must be installed in conjunction with
the separate power supply enclosure supplied,
which is intended for permanent connection to
the mains electrical supply. The unit and the
power supply enclosure are intended for fixed
wiring installation.
4. The power supply enclosure requires free air
circulation for effective operation It must not be
recessed into the mounting surface or covered
with any form of insulation, which might be used in
a ceiling or roof void.
5. Wiring to the unit in the U.K. must be via
the switched fused spur supplied as part of the
power supply enclosure.
6. The spur supplied is designed with a
minimum contact gap of 3mm in all poles.
7. Ensure that the mains electrical supply is
compatible with the rating label attached to the
product.
8. The unit must be sited such that the ambient
temperature will not exceed 40°C.
9. Screwdriver access must be provided to the
left of the power supply enclosure for the
removal of the cover screw (Fig. 2).
10. Do not site the appliance in the vicinity of
excessive levels of airborne oil or grease. or
directly over a cooker.
11. If the unit is installed in a room containing a
fuel burning appliance, the installer must ensure
that air replacement is adequate for both
appliances.
12. The unit must not be installed at a level
below 500mm from the floor.
13. The internal grille surround must be sited at
least 125mm away from the room ceiling (Fig. 3).
and 300mm away from any adjacent vertical
surface.
14. The external cowl of the unit must be sited
at least 500mm away from any flue of gas or
solid fuel appliances. This is to avoid back flow
of gases entering the room.
15. All safety regulations and requirements
must be strictly followed to prevent hazards to
life and property both during and after
installation and during subsequent maintenance
or servicing.
16. Ensure the mains electrical supply is
switched off before commencing installation or
maintenance.
2.0 Site Requirements
4