1.1.6 Setting of the internal standard interface

The default setting of the baud rate is
4800. The message on the right is
indicated for information purposes:

1.1.7 Programming of relay outputs for error messages

The main clock is fitted with 2 relay outputs that can be programmed for the following error
messages:
Supply:
power supply failure (24 V DC)
Ext. Fuse: failure of the secondary clock fuse ("SLAVE")
Int. Fuse: failure of the main fuse ("MAINS")
Low Batt.: accumulator voltage too low
Programming of the relay outputs for the error messages:
1. Remove the write protection (
2. Press the key 1 several times until
one of the two relay setting menus
appears on the display, for example:
3. Press the ENTER key for confirmation. The cursor starts flashing.
4. Press the key 2 to select from among the possible errors.
5. Press the ENTER key to confirm the selection.
To cancel the modification, press the MENUE key twice.
6. Press the MENUE key, to return to the date display.

1.3 Set-up of secondary clocks

1. Press the MENUE key for at least 4 s until the version number appears on the display.
2. Press the key 2 several times until
the analogue time setting menu
appears on the display.
3. Press the ENTER key. The following
display appears (for secondary
clocks on the terminals 32 & 33):
For analogue secondary clocks on
the terminals 7 & 8, press 1 or 2
once, until the message on the right
appears on the display:
4. Press the ENTER key. The following
display appears:
5. Set all secondary clockss by hand to a standardised time (e.g. 12:00).
V3.0 01/2011
WEMPE digital main clock 20097
1.1.1).