Manitowoc QuietQube Indigo Series Technician's Handbook page 174

Ice machines
Hide thumbs Also See for QuietQube Indigo Series:
Table of Contents

Advertisement

5. Ohm Ice Thickness Probe
NOTE: Verify meter leads are properly connected to
VOM with the red meter lead connected to positive &
the black meter lead connected to negative
Disconnect Ice Thickness Probe from control
board
Connect red meter lead to the red wire and the
black meter lead to the black wire - Normal
readings = 1.4 to 2.5 KΩ's.
Reverse leads - Connect black meter lead to the
red wire, red meter lead to the black wire - Normal
readings = 1.2 to 1.5 KΩ's.
Ohm values are within range - Check control board
Pass
voltage at the ice thickness probe connection.
Fail
6. Check control board voltage
Set VOM to DC voltage scale - Check voltage
across the top and bottom pin - Normal readings =
3.25 to 3.35 VDC.
Pass
Fail
174
Replace ice thickness probe.
Control board voltage is normal
Replace control board
Part Number STH026 8/12