Mitsubishi Electric Mr.Slim PUH-P25VGAA Service Manual page 61

Split-type, heat pump air conditioners, r407c, outdoor unit
Hide thumbs Also See for Mr.Slim PUH-P25VGAA:
Table of Contents

Advertisement

SW2 setting
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Outdoor piping temperature/Cond./Eva.
ON
(TH6)
– 39~88
1
2 3 4 5 6
Discharge super heat. SHd
0~255
ON
Cool = TH4-TH6
1
2 3 4 5 6
Heat = TH4-TH5
Sub cool. SC
0~130
ON
Cool = TH6-TH3
1
2 3 4 5 6
Heat = TH5-TH2
Communication demanded capacity.
0~255
ON
1
2 3 4 5 6
When no communication demanded
setting, "100" is displayed.
Error thermistor display
ON
1
2 3 4 5 6
Fan step on error occurring.
ON
0~16
1
2 3 4 5 6
LEV opening on error occurring
0~440
ON
Display by scaled 1/5 to actual opening
1
2 3 4 5 6
Outdoor piping temperature/Cond./Eva.
on error occurring. (TH6)
ON
– 39~88
1
2 3 4 5 6
Discharge super heat on error occurring.
SHd
ON
0~255
Cool = TH4-TH6
1
2 3 4 5 6
Heat = TH4-TH5
Sub cool on error occurring. SC
0~130
ON
Cool = TH6-TH3
1
2 3 4 5 6
Heat = TH5-TH2
Display detail
When air conditioners are
connected to M-NET and
under central control.
Explanation for display
17~30
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns)
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) 115 :
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
0~255
(When the capacity is 100 or more, the hundreds
digit and tens, units digit are displayed by turns)
(Example) When 100
3: Outdoor liquid piping thermistor (TH3)
6: Outdoor condenser thermistor (TH6)
When no error thermistor, "–" is
displayed.
0~16
0~440
(When the pulse is 100 or more, the hundreds digit
and tens, units digit are displayed by turns)
(Example) When the display shows 300.
300
5 = 1500 pulse
– 39~88
(When the thermistor is 0:and less, "–" and
temperature are displayed by turns.)
(Example) When –15:
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 150:
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 115:
61
One second interval.
1
15
One second interval.
1
00
One second interval
15
One second interval
1
50
One second interval
1
15
Unit
:
:
:
:
%
Code
Step
Pulse
:
:
: