Cooling only type
Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Volts
Amperes
Outdoor unit
Phase , Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/f
PLA-RP35AA
Cooling
W
4,500
kW
1.72
PLA-RP35AA
1 , 50
V
230
A
0.79
PU-P35VGAA.UK
PU-P35YGAA.UK
1/3 , 50
V
230/400
A
7.43/1.94
MPa
2.01
MPa
0.59
°C
78
°C
48
°C
11
m
°C
D.B.
27
°C
W.B.
19
°C
D.B.
14.1
°C
D.B.
35
°C
W.B.
24
0.75
0.16
f )
PLA-RP50AA
Cooling
5,600
2.53
PLA-RP50AA
1 , 50
230
0.79
PU-P50VGAA.UK
PU-P50YGAA.UK
1/3 , 50
230/400
11.30/3.23
2.48
0.59
85
55
10
5
27
19
14.6
35
24
0.82
0.12
16
PLA-RP60AA
Cooling
6,700
2.57
PLA-RP60AA
1 , 50
230
0.79
PU-P60VGAA.UK
PU-P60YGAA.UK
1/3 , 50
230/400
11.49/3.29
2.18
0.54
80
51
5
27
19
12.9
35
24
0.72
0.14
9
5