10-3-4. Malfunction-diagnosis method by wireless remote controller

<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
CHECK
CHECK
display
TEMP
ON/OFF
ON/OFF
button
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK LOUVER
CHECK
TEST RUN
min
button
RESET
SET
CLOCK
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the temperature
Temperature
buttons.
button
3. Point the remote controller at the
HOUR
sensor on the indoor unit and
button
h
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
35
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.