Mitsubishi Electric Mr.Slim PUH-P25VGAA Service Manual page 10

Split-type, heat pump air conditioners, r407c, outdoor unit
Hide thumbs Also See for Mr.Slim PUH-P25VGAA:
Table of Contents

Advertisement

Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
A
A
kW
W
kW
K/min(CFM)
Cooling
dB
W
mm(in.)
D
mm(in.)
H
mm(in.)
kg(lbs)
kg(lbs)
L
Liquid
mm(in.)
Gas
mm(in.)
Indoor side
Outdoor side
Height difference
Piping length
PU-P125YGAA.UK
Cooling
3-ph, 50Hz,400V(4wires)
7.52
18.0
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
BE82YADMT
3.5
Line start
Thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07+0.07
95(3,360)
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
4.6(10.1)
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
10
PU-P140YGAA.UK
Cooling
8.92
20.4
BE96YADMT
4.2
100(3,530)
57
4.9(10.8)