Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Volts
Amperes
Outdoor unit
Phase , Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/f
PLA-RP71AA
Cooling
W
7,700
kW
3.42
PLA-RP71AA
1 , 50
V
230
A
0.79
PU-P71VGAA.UK
PU-P71YGAA.UK
1/3 , 50
V
230/400
A
15.55/4.64
MPa
2.30
MPa
0.47
°C
81
°C
44
°C
5
m
5
°C
D.B.
27
°C
W.B.
19
°C
D.B.
13.4
°C
D.B.
35
°C
W.B.
24
0.74
0.13
f )
17
PLA-RP100AA
PLA-RP125AA
Cooling
Cooling
9,200
13,300
3.68
PLA-RP100AA
PLA-RP125AA
1 , 50
230
1.25
PU-P100VGAA.UK
PU-P125YGAA.UK
PU-P100YGAA.UK
1/3 , 50
230/400
16.33/4.59
1.98
0.54
71
42
8
5
27
19
14.0
35
24
0.78
0.12
PLA-RP140AA
Cooling
14,200
5.09
5.90
PLA-RP140AA
1 , 50
1 , 50
230
230
1.64
1.64
PU-P140YGAA.UK
3 , 50
3 , 50
400
400
6.44
7.73
2.27
2.11
0.45
0.48
81
71
45
41
2
6
5
5
27
27
19
19
11.3
11.7
35
35
24
24
0.69
0.72
0.09
0.06