Mitsubishi Electric Mr.Slim PUH-P25VGAA Service Manual page 58

Split-type, heat pump air conditioners, r407c, outdoor unit
Hide thumbs Also See for Mr.Slim PUH-P25VGAA:
Table of Contents

Advertisement

SW2 setting
Piping temperature. (TH3)
– 40~90
ON
1
2 3 4 5 6
Discharge temperature. (TH4)
0~216
ON
1
2 3 4 5 6
FAN output step.
0~16
ON
1
2 3 4 5 6
The number of ON / OFF times.
0~9999
ON
1
2 3 4 5 6
Compressor integrating operation times.
0~9999
ON
1
2 3 4 5 6
Compressor operating current.
0~40
ON
1
2 3 4 5 6
LEV opening.
0~440
ON
1
2 3 4 5 6
New error postponement code.
New outdoor unit error postponement
ON
display.
1
2 3 4 5 6
Operation mode on error occurring.
ON
1
2 3 4 5 6
Display detail
Explanation for display
– 40~90
(When the coil thermistor is 0:or below, "–" and
temperature displays by turns.)
(Example) When -10:
One second interval
0~216
(When the discharge thermistor is 100 or more, the
hundreds digit and tens, units digit are displayed by
turns.)
(Example) When 150:
One second interval
1
0~16
0~9999
(When the number of times is 100 or more, the
hundreds digit and tens, units digit are displayed by
turns.)
(Example) When 42500 times
One second interval
4
0~9999
(When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 2450 hours
One second interval
2
0~40
Output pulse is displayed by one fifth of actual value.
(Example) When the display shows 300
300
5 = 1500 pulse
1500 pulse is the actual output pulse
No postponement code is "00".
Operation mode on error stop.
SW2 setting is displayed at below code.
(SW2)
ON
1
2 3 4 5 6
58
Unit
:
10
:
50
Step
100 times
25
10 hours
45
A
Pulse
Code
display
Code
display