Dc Voltage Connection - Platinum 22000 tl Installation And Operating Manual

Tl series
Table of Contents

Advertisement

PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Mounting
Note
Note
24
Installation and operating manual: PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Version 05/2010
Mat. No. 737 576-AB

DC voltage connection

1
1
2
3
4
Fig. 11 DC voltage connection
(1) DC disconnector
(2) DC terminal -
(3) DC terminal +
(4) Fan
PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL are
equipped with three MPP trackers working separately, with three
connection areas for direct voltage.
Distribute strings of PV generator among the three areas so that
there are the same module types with the same horizontal
orientation and vertical tilt and approximately the same DC
power connected in every area.
there is no electrical connection between the three areas.
Allocate DC connectors within the same area in pairs (+ and -).
It is possible that DC powers of different connection areas differ.
Establish DC voltage connection as follows:
Establish a connection to the solar panel on the DC input with a
cable with a DC plug connector.
Use exclusively DC cable connectors and DC receptacles of the
same type and manufacturer.
Make sure that cable connector in latched in socket correctly.
Put protective caps on unused plug connectors.
1
4
2 3
1
2 3
4