Controls
Remote Wall Mounted Thermostats
Wall mounted thermostats are available for the Applied
PTAC unit in automatic or manual changeover styles.
All include a fan switch for constant "on" operation or
"automatic" for cycle operation with a call for heat or
cooling. All thermostats are 24-volt type and have dual
Fahrenheit and Celsius temperature setpoint scales.
Non-Programmable Heat/Cool Manual
Changeover Thermostat (107095701)
Simple to operate, single push button for one-stage
heating and cooling, or single stage heat pump. Zone
compatible, and 4- or 5 wire compatible (terminal "C" is
optional for non-heat pump systems). System "heat-off-
cool" switch and fan "on-off" switch.
Figure 27. Non-Programmable Thermostat (107095701)
Specifications
Electrical Rating:
•
24 VAC (18 to 30 VAC)
•
1 amp maximum per terminal
•
3 amp maximum total load
•
60-minute power backup (SC2001)
Temperature Control Ranges:
•
45
F to 90
F, Accuracy: ±1
o
o
System Configurations:
•
1 stage heat, 1 stage cool or single stage electric
heat pump
Terminations:
•
R, C, W, Y, O, B, G
IM 882 / Page 26 of 36
F
o
7-Day Programmable Manual Changeover
Thermostat (107095801)
Simple, logical programming for set-up and set-back
temperatures and times. Compatible with single-stage
heat pump systems. Enables separate morning, day,
evening, and night settings for every day of the week.
Simpleset™ feature enables easy copying of one day's
programming for the entire week. Select a warmer or
cooler setting any time to temporarily override any
program setting. Vacation hold overrides programming.
Clear backlit display makes it easy to see time,
temperature and setpoint – even in the dark. No batteries
required.
Figure 28. 7-Day Programmable, Manual Changeover
Thermostat (107095801)
Specifications
Electrical Rating:
•
24 VAC (18 to 30 VAC)
•
1 amp maximum per terminal
•
3 amp maximum total load
•
60-minute power backup (SC3001)
•
Easy access terminal block
Temperature Control Ranges:
•
45
F to 90
F, Accuracy: ±1
o
o
System Configurations:
•
Single stage heat, single stage cool or single stage
electric heat pump
Terminations:
•
RC, RH, C, W, Y, O, B, G
F
o