Introduction

McQuay offers the most complete line of PTAC and
PTHP products for new construction projects and
exact replacements for our original Singer, Remington,
American Air Filter and American Standard brand
equipment, and models from other manufacturers.
McQuay products feature our proven institutional grade
design and construction that allows you to benefit from
the long life, reliability, and low sound levels, along
with higher energy efficiencies for lower operating costs.
Plus, McQuay offers a nationwide network for original
equipment replacements with local parts and service.
McQuay
Applied Packaged Terminal Air Conditioners
®
and Heat Pumps are designed and built for through-the-
wall installation in either new or existing buildings. The
Figure 1. Exploded View of the 16" x 42" PDAC/PDHP with Top-Mounted Hydronic Unit
Room Cabinet
Removable Front Panel
Top-Mount Hydronic Heat Section
Cooling Chassis
self-contained refrigerant system delivers cooling to the
desired space. Heating can be accomplished with electric
resistance, with hydronic (water or steam), hydronic
with intermediate electric resistance or with reverse
cycle technology (heat pump models only). Generally,
an estimate for capacity selection is 35 BTUH per square
foot of floor space (cooling) and 4 BTUH (1.25 watts)
per cubic foot (heating). The architect or engineer must
verify the selection. Note that the heat pump reverse
cycle generates approximately 10 BTUs per electrical
watt as compared to 3.4 BTUs per watt with resistance
electric heat. The unit will restart at its last setting after a
power interruption.
Premium Digital Touchpad Control
Louver (Architectural)
16" x 42" Wall Sleeve