Digital Touchpad With Automatic Changeover From Cooling To Heating & Heating To Cooling - McQuay PDAA Installation & Maintenance Data

Dual motor angled top unit - 16" x 42" with r-410a refrigerant
Table of Contents

Advertisement

Digital Touchpad with Automatic
Changeover from Cooling to Heating &
Heating to Cooling
AUTO
Available with the Programmable LUI (668003801)
and Premium Board (667997301) only. The Auto-
Changeover board has a new control set with a
touchpad label that shows, "AUTO". The Auto
Changeover control provides:
Auto changeover from heat to cool and vice versa
LED's from top down that read: Sleep, Cool, Auto,
Fan, and Heat
AUTO Non-Programmable Mode:
Display shows both HEAT and COOL icons
Temperature set point displays between the HEAT
and COOL icons
Setpoint is adjusted with Up and Down arrows
Heating initiates when the room temperature falls
one degree below the thermostat setpoint. Heating
terminates when the room temperature reaches two
degrees above the setpoint
Cooling initiates when the room temperature
reaches one degree above the thermostat setpoint.
Cooling terminates when the room temperature
falls two degrees below the setpoint
AUTO Programmable Mode:
HEAT and COOL icons alternatively flash with
their respective programmed setpoints
The system engages cooling and heating automati-
cally to maintain respective setpoints according to
system model selection
The 2-degree gap between setpoints represents the
deadband and is necessary to prevent unecessary
switching between heating and cooling
The 2 degree deadband provides the following:
Heating activates when the room temperature is
one degree below the thermostat setpoint plus the
2 degree deadband.
Cooling activates when the room temperature is
one degree above the thermostat setpoint plus the
2 degree deadband
Keys and Indicators Labels
ON/OFF, FAN SPEED, MODE,
FAN MODE, SLEEP, PROG-ON/OFF
8 Push Buttons
Temp buttons:
Temp UP and
SLEEP, COOL, AUTO, FAN,
9 LED Indicators
HEAT, HIGH, LOW, CYCLE, CONT.
LED 2 Digit Displays No Label
IM 934-2 Applied PDAA/PDHA / Page 29 of 44
for
for Temp DOWN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

PdhaPdac seriesPdhp series

Table of Contents