Controls; Standard Digital Touchpad Control - McQuay PDAE Installation & Maintenance Data

16" x 44" replacement unit comfort conditione
Table of Contents

Advertisement

Controls (Non-programmable)

Standard Digital Touchpad Control

Figure 14. Standard Digital Touchpad Control
Application
The PTAC Digital Control is used to control
a PTAC Unit that includes both an integral air
conditioner and a source of heat.
The Digital Control is operated with a Touchpad.
Inputs and Outputs
Indoor coil sensor, (ICS)
Outdoor coil sensor, (OCS)
Indoor air sensor, (IAS)
Outdoor air sensor, (OAS)
Remote T'stat, T'STAT (RCWYBG)
Heat Fan Lock Out (HFLO)
Power supply, (24VAC)
Line voltage input, (L1, L2)
Indoor fan standby voltage, (L1STB L2STB)
Control selection, (LUI, T'STAT
Model selection, (AC/E, HP, HP/E)
Time delay bypass, (TEST)
Indoor off fan cycle, (FAN, OFF CYCLE–10, 20,
30, 1 HR)
Outputs
Compressor output, COM
Indoor fan, BLOWER LO, HI
Outdoor fan, OUTDOOR FAN
Electric heater, ELE
Reversing valve, REV VALVE
Figure 15. Standard Digital Control Indicators
9- LED
Indicators
User Interface
The user will by default control the Electronic
Controller via the touchpad. The user can select with
a jumper for the unit to receive commands from a
Keys and Indicators Labels
7 Push Buttons
9 LED Indicators
LED 2 Digit Displays No Label
Display Function Legend
Tr = Room Temperature
hI = High Room Temperature
Lo = Low Room Temperature
LA = Low Ambient Lockout
rT = Remote Thermostat Control
tP = Touchpad Control
t
= Time
Ts = Temperature Setpoint
Rf = Room Freeze Condition
CF = Coil Freeze Protection
F = Fahrenheit
C = Celsius
LC = Control Lockout Mode
Remote Thermostat Control
The Remote Thermostat can be any thermostat
that can interface with an electronic thermostat via
RCWYBG terminals. The Control Selection jumper
must be in T'STAT position. During a call the remote
thermostat will pass R back to the controller on a
respective terminal. The push buttons on the touchpad
become inactive in the remote thermostat mode.
However, the control pad LED display will indicate
the mode of operation, and the room temperature.
Note:
In terms of outputs, there are two types of thermostats:
relay contacts and solid state.
If you open the thermostat and don't see relays then it
must be solid state.
Manufacturers of solid state output thermostats in-
clude loading resistors on their installation kits. They
LED
are of 560 Ohm and 3W value. These resistors are
2-Digit Display
meant to load thermostat solid state outputs in order
for the output voltage to be either 0 or 24VAC, i.e. no
floating voltage. These resistors are connected from W,
7- Push Buttons
Y, G to common (C), respectively.
You can wire any type of 24Vac thermostat straight
into the remote thermostat connector of PTAC control
boards, 667997101 and 667997201 (Basic and Pre-
mium models) and the control boards will recognize
the signals from them.
ON/OFF, FAN SPEED, MODE
FAN MODE, SLEEP
Temp buttons:
for
for Temp DOWN
Temp UP and
SLEEP, COOL, COOL/DRY, FAN,
HEAT, HIGH, LOW, CYCLE, CONT.
IM 950-1 / Page 15 of 38