Controls
Premium (Programmable) Digital Touchpad
Control Operating Instructions
9-LED Indicators
Application
The PTAC Digital Control is used to control
a PTAC Unit that includes both an integral air
conditioner and a source of heat.
The Digital Control is operated with a Touchpad.
Inputs and Outputs
Indoor coil sensor, (ICS)
Outdoor coil sensor, (OCS)
Indoor air sensor, (IAS)
Outdoor air sensor, (OAS)
Remote T'stat, T'STAT (RCWYBG)
Power supply, (24VAC)
Line voltage input, (L1, L2)
Indoor fan standby voltage, (L1STB L2STB)
Control selection, (LUI, T'STAT
Model selection, (AC/E, HP, HP/E)
Time delay bypass, (TEST)
Indoor off fan cycle, (FAN, OFF CYCLE–10, 20,
30, 1 HR)
Outputs
Compressor output, COM
Indoor fan, BLOWER LO, HI
Outdoor fan, OUTDOOR FAN
Electric heater, ELE
Reversing valve, REV VALVE
User Interface
The user will by default control the Electronic
Controller via the touchpad. The user can select with
a jumper for the unit to receive commands from a
Remote Thermostat.
IM 934-2 Applied PDAA/PDHA / Page 28 of 44
Keys and Indicators Labels
ON/OFF, FAN SPEED, MODE,
8 Push Buttons
FAN MODE, SLEEP, PROG-ON/OFF
Temp buttons:
Temp UP and
9 LED Indicators
SLEEP, COOL, COOL/DRY, FAN,
HEAT, HIGH, LOW, CYCLE, CONT.
LED 2 Digit Displays No Label
Display Function Legend
Tr = Room Temperature
hI = High Room Temperature
Lo = Low Room Temperature
LA = Low Ambient Lockout
rT = Remote Thermostat Control
tP = Touchpad Control
t
= Time
Ts = Temperature Setpoint
Rf = Room Freeze Condition
CF = Coil Freeze Protection
F = Fahrenheit
C = Celsius
LC = Control Lockout Mode
Remote Thermostat Control
The Remote Thermostat can be any thermostat
that can interface with an electronic thermostat via
RCWYBG terminals. The Control Selection jumper
must be in T'STAT position. During a call the remote
thermostat will pass R back to the controller on a
respective terminal. The push buttons on the touchpad
become inactive in the remote thermostat mode.
However, the control pad LED display will indicate the
mode of operation, and the room temperature.
LED with Program
Setting Display
8- Push Button
Display Inputs
for
for Temp DOWN

Hide quick links: