Installation of Basic Wall Sleeve
5. Recess the wall sleeve so that the louver is flush
with the exterior of the building.
6. Level wall sleeve left to right and pitch 1/4" front
to back to the outside and secure by anchoring
with appropriate fasteners or drill additional holes
as required to secure firmly. Refer to Anchoring
The Wall Sleeve instructions on
page 13.
CAUTION
DO NOT drill holes in the bottom of the wall sleeve as it
will cause leaks.
7. Where a subbase is used, secure wall sleeve to
subbase with clips provided.
8. Caulk the wall sleeve to the wall opening on both
the inside and outside perimeter. Be careful not to
plug the weep holes. Caulking should be resilient,
nonhardening type such as silicone.
Figure 19. Panel wall construction with standard electrical
subbase
Louver Frame
(see page 11 for details)
Wall Sleeve
8
"
1
/
4
(209mm)
17"
16"
(432mm)
(406mm)
Room
Electrical
Cabinet
Subbase
See Note
Floor
Power Supply Connect
(Alternate Entry)
Note: Standard subbase is available in 3" or 4"
(76 mm or 102 mm) height. Leveling legs
provide adjustment of 1" (25 mm).
Attaching Wall Sleeve to Subbase
1. Where a subbase is used, secure wall sleeve to
subbase with clips provided.
2. Caulk the wall sleeve to the wall opening on both
the inside and outside perimeter. Be careful not to
plug the weep holes. Caulking should be resilient,
nonhardening type such as silicone.
13
"
3
/
4
(349mm)
Subbase Side Channel
3. Secure the two sections by installing the clip
screws supplied with the hardware bag.
4. Caulk indoor/outdoor perimeter of wall sleeve
with resilient caulk such as silicone.
5. Finish any uncompleted electrical and/or plumbing
connections.
Figure 20. Panel wall construction with cord connection
(see page 11 for details)
(209mm)
17"
(432mm)
Room
Cabinet
3"Min. (76mm)
Outside
Floor
Louver
Receptacle
(by others)
Figure 21. Panel wall installation with hydronic subbase
Gasket
& Caulk
(see page 11 for details)
Perimeter
(209mm)
17"
Room
(432mm)
Cabinet
Hydronic
Heating
8
"
1
/
4
(209mm)
Power Supply Connect
(Alternate Entry)
Leveling Legs with 1" Adjustment
Louver Frame
8
"
13
"
1
/
3
/
4
4
(349mm)
16"
(406mm)
Wall Sleeve
Conduit
Minimum
2 Supports
(field supplied)
Louver Frame
13
"
8
"
1
3
/
/
4
4
(349mm)
16"
(406mm)
Wall Sleeve
Coil
Subbase
Side
Channel
IM 934-2 Applied PDAA/PDHA / Page 15 of 44
Outside
Louver
Caulk
Perimeter
both Indoors
& Outdoors
Outside
Louver
Caulk
Perimeter
both Indoors
& Outdoors