4.3 Chimney Installation Notes 
1. If  possible,  install  an  interior  chimney  as  it  will  provide  better  performance.  In  areas  with  continuous 
temperatures below 18 C (0 F), the use of an exterior chimney increases the likelihood of operating 
problems such as low draft, high rate of creosoting, and poor start‐up characteristics. Exterior chimneys 
are also prone to down‐drafting and flow reversal. Installations, which are located on lower floors in the 
house,  such  as  in  a  basement,  in  combination  with  outside  chimney,  are  especially  prone  to  flow 
reversal. 
2. The ME300 is listed only with chimney systems described in table 1. 
3. A chimney venting a fireplace shall not vent any other appliance. 
4. The minimum chimney system height for a straight installation is 15 ft. (4,5 m). 
5. All chimney installations must include at least one support. Reducing the amount of chimney weight on 
the  fireplace  will  help  avoid  the  noise  created  when  the  fireplace  expands.  This  can  be  achieved  by 
having the chimney supported by the supports. The maximum chimney length that should be supported 
by the fireplace is 12 ft. (3.7 m) for 1" Solid Pack Chimney.  
6. The chimney must extend at least 3 ft. (92 cm) above its point of contact with the roof and at least 2 ft. 
(61 cm) higher than any wall, roof or building within 10 ft. (3.1 m) of it. See figures bellow to determine 
the configuration that applies to your roof (flat or sloped roof and the distance between the chimney 
and the highest point of the roof and/or the nearest chimney). 
 
ME300 ‐ Installation and Operation Manual
 
 
 