3.8 Compliance of a Combustible Mantel Shelf 
To ensure compliance of an existing mantel 
shelf  or  to  install  a  combustible  mantel 
shelf,  refer  to  table  and  figure  in  this 
section. For example, a mantel shelf with a 
6''  depth  (152  mm)  ((C)  value)  must  be 
installed at least 48" (1219 mm) ((B) value) 
above  the  bottom  of  the  fireplace  (see 
figure  and  tables  in  this  section).  Different 
mantel  shelf  dimensions  are  listed  in  the 
following  table.  However,  no  combustible 
mantel  shelf  can  be  installed  at  less  than 
48"  (1219  mm)  above  the  bottom  of  the 
fireplace.  If the depth of the mantel shelf is 
not listed in the table below, add 42" (1067 
mm)  to  the  depth  of  your  mantel  shelf  to 
obtain  the  safe  positioning  of  your  mantel 
shelf.  For  example,  for  a  9"  (229  mm) 
mantel shelf, the safe positioning would be 
51"  (1295  mm)  above  the  bottom  of  the 
fireplace 42" (1067 mm) + 9" (229 mm)). 
 
 
 
24 
 
CLEARANCES 
72" (1829 mm) 
 
SHELF POSITIONING 
48" (1219 mm) 
50" (1270 mm) 
52" (1321 mm) 
54" (1372 mm) 
ME300 ‐ Installation and Operation Manual 
6" (152 mm) 
8" (203 mm) 
10" (254 mm) 
12" (305 mm) 