Rough-In Dimensions; Foreword - State Water Heaters Ultra Forcce SUF 60 120 Installation & Operation Manual

Commercial gas water heater
Hide thumbs Also See for Ultra Forcce SUF 60 120:
Table of Contents

Advertisement

GAS VALVE PIPING
SUF-120
1/2" NPT
SUF-150,
199 & 250
3/4" NPT
Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P.
Input
Model
BTU/Hr.
SUF 60 120NE
125,000 Nat.
SUF 60 120PE
120,000 L.P.
SUF 100 150NE
150,000 Nat.
SUF 100 150PE
150,000 L.P.
SUF 100 199NE
199,000 Nat.
SUF 100 199PE
199,000 L.P.
SUF 100 240NE
240,000 Nat.
Input
Model
Kwh
SUF 60 120NE
37
SUF 60 120PE
35
SUF 100 150NE
44
SUF 100 150PE
44
SUF 100 199NE
59
SUF 100 199PE
59
SUF 100 240NE
70
Recovery capacities are based on heater performance at 94% thermal efficiency.
These designs comply with the current edition of the American National
Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 as
an automatic circulating tank water heater, and automatic storage water
heaters.
Detailed installation diagrams are found in this manual. These diagrams
will serve to provide the installer with a reference for the materials and
methods of piping necessary. It is highly essential that all water, gas
piping and wiring be installed as shown on the diagrams.
Particular attention should be given to the installation of thermometers at
the locations indicated on the diagrams as these are necessary for
checking the proper functioning of the heater.
ROUGH-IN-DIMENSIONS
Approx.
TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR
Gallon
Capacity
30
40
50
60
475
356
285
60
456
342
274
100
570
427
342
100
570
427
342
100
759
569
456
100
759
569
456
100
912
684
547
Approx.
Liter
Capacity
17°C
22°C
28°C
227
1798
1348
1079
227
1726
1295
1037
379
2158
1616
1295
379
2158
1616
1295
379
2873
2154
1726
379
2873
2154
1726
379
3452
2589
2071

FOREWORD

60
70
80
237
203
178
228
195
171
285
244
214
285
244
214
380
325
285
380
325
285
456
391
342
TEMPERATURE RISE - DEGREES °C - LITERS PER HOUR
33°C
39°C
44°C
898
768
674
863
738
647
1079
924
810
1079
924
810
1438
1230
1079
1438
1230
1079
1726
1480
1295
In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local area
where the installation is to be made. These shall be carefully followed in all
cases. Authorities having jurisdiction should be consulted before installations
are made.
In the absence of local codes, the installation must comply with the latest
editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National
Electric Code, NFPA 70 . The former is available from the CSA International,
8501 East Pleasant Valley Road, Cleveland, OH 44131, and both documents
are available from the National Fire Protection Association, 1 Batterymarch
Park, Quincy, MA 02269.
2
90
100
110
120
158
142
129
119
152
137
124
114
190
171
155
142
190
171
155
142
253
228
207
190
253
228
207
190
304
274
248
228
50°C
56°C
61°C 67°C
598
538
488
450
575
519
469
432
719
647
587
538
719
647
587
538
958
863
784
719
958
863
784
719
1151
1037
939
863
130
140
110
102
105
98
132
122
132
122
175
163
175
163
210
195
72°C 78°C
416
386
397
371
500
462
500
462
662
617
662
617
795
738