Dimensions And Capacities Data; Table 1 - Rough-In Dimensions; Table 2 - Recovery Capacities; U.s. Gallons/Hr And Litres/Hr At Temperature Rise Indicated - State Water Heaters PCE-6 10MSA Instruction Manual
Series 102, series 110, commercial electric water heaters
Recovery capacities at 100° F rise equal: for non-simultaneous element operation = 4.1 gal. x KW of one element; for simultaneous element operation = 4.1 gal. x 2/3 KW of
both elements. For other rises multiply element KW as previously explained by 410 and divide by temperature rise. Full load current for single phase = total watts : voltage.
table 1 - rouGh-In dIMensIons
a
litres
inches
mm
23
15 1/2
394
38
18 1/4
464
57
26
660
76
22 1/4
565
114
30 7/8
784
151
32 1/4
819
189
32 1/4
819
114
34 1/2
876
151
45 1/8
1146
189
54 7/8
1394
250
60 3/4
1543
303
59 3/8
1508
450
62 7/16
1586
table 2 - recoVery capacItIes
u.s. Gallons/hr and litres/hr at teMperature rIse IndIcated