Error Codes; Fault Conditions; No Incoming Line Voltage; No Low Voltage - State Water Heaters Ultra Forcce SUF 60 120 Installation & Operation Manual

Commercial gas water heater
Hide thumbs Also See for Ultra Forcce SUF 60 120:
Table of Contents

Advertisement

Possible Cause
1. Burner ground wire broken
or corroded
2. Connectors unplugged
3. Igniter broken
4. Flame probe faulty
5. Gas shut off
6. Clogged gas valve
7. Faulty gas valve
8. Defective control
9. Burner improperly adjusted
10. Dirty burner

FAULT CONDITIONS

The controller is set up to provide additional status indicators under Fault
Conditions. The following figures are possible Fault Conditions.
NO INCOMING LINE VOLTAGE (Figure 19) Line LED Off
NO INCOMING LINE VOLTAGE, Line LED Off
Possible Cause
1. No Input Power
2. Wiring Disconnected
3. One or more wiring receptacles
disconnected from control
4. LED burned out
Remedy
1. Check wire and connection
at burner
2. Check connections
3. Replace igniter
4. Replace flame probe
5. Turn on gas supply
6. Replace gas valve
7. Replace gas valve
8. Replace control
9. Adjust burner
10. Clean burner
FIGURE 19
Remedy
1. Apply Power
2. Check all wiring
3. Reconnect plugs on control,
confirm all are fully seated
4. Ignore or replace control
NO LOW VOLTAGE (Figure 20)
24V AC LED Off
NO LOW VOLTAGE, 24V AC LED Off
Possible Cause
1.Blower 24 VAC Fuse
2.Defective Transformer
3.LED burned out
TEMPERATURE PROBE FAULT (Figure 21)
Water Temp LED Flashing
TEMPERATURE PROBE FAULT, Water Temp LED Flashing
This condition accommodates multiple failure modes. To more accurately
determine the cause of failure, press the pushbutton on the display board.
16
FIGURE 20
Remedy
1. Replace 24 VAC 3a Fuse
(Littlefuse 257003 automotive fuse).
2. Replace Transformer
3. Ignore or replace control
FIGURE 21