Hard Water; Air Requirements; Mechanical Exhausting Of Room Air; Unconfined Space - State Water Heaters Ultra Forcce SUF 60 120 Installation & Operation Manual

Commercial gas water heater
Hide thumbs Also See for Ultra Forcce SUF 60 120:
Table of Contents

Advertisement

A service clearance of 24" (61 cm) should be maintained from serviceable
parts such as relief valves, flue baffles, flue damper devices, thermostats,
cleanout openings or drain valves.
Always disconnect electrical power before servicing the unit
*ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN
ALCOVE

HARD WATER

Where hard water conditions exist, water softening or the threshold type of
water treatment is recommended. This will protect the dishwashers, coffee
urns, water heaters, water piping and other equipment.
See MAINTENANCE section for details of tank cleanout procedure.

AIR REQUIREMENTS

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS,
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR.
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND
VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE
RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN
CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH A CONDITION
OFTEN WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS
AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION.

MECHANICAL EXHAUSTING OF ROOM AIR

Where an exhaust fan is installed in the same room with a heater, sufficient
openings for air must be provided in the walls.
WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE HEATER'S
VENTING SYSTEM, CAUSING POOR COMBUSTION. SOOTING MAY RESULT
IN SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR EXPLOSION.
IT CAN ALSO CREATE A RISK OF ASPHYXIATION.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined
spaces may provide adequate air for combustion and ventilation.
If the unconfined space is within a building of tight construction (buildings
using the following construction: weather stripping, heavy insulation,
caulking, vapor barrier, etc.), air for combustion and ventilation must be
obtained from outdoors. The installation instructions for confined spaces
in tightly constructed buildings must be followed to ensure adequate air
supply.

CONFINED SPACE

When drawing combustion air from inside a conventionally constructed
building to a confined space, such a space shall be provided with two
FIGURE 4
WARNING
UNDERSIZED OPENINGS
permanent openings, ONE IN OR WITHIN 12 INCHES (31 cm) OF THE
ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (31 cm) OF THE
ENCLOSURE BOTTOM. Each opening shall have a free area of at least one
square inch (6.5 cm²) per 1000 Btuh appliances in the enclosure, but not
less than 100 square inches (645 cm²).
If the confined space is within a building of tight construction, air for
combustion and ventilation must be obtained from outdoors. When
directly communicating with the outdoors through vertical ducts, two
permanent openings, located in the above manner, shall be provided.
Each opening shall have a free area of not less than one square inch
(6.5 cm²) per 4000 Btuh of the total input of all appliances in the
enclosure. If horizontal ducts are used, each opening shall have a
free area of not less than one square inch (6.5 cm²) per
2000 Btuh of the total input of all appliances in the enclosure.

CHEMICAL VAPOR CORROSION

CORROSION OF THE FLUE WAYS AND VENT SYSTEM MAY OCCUR IF AIR
FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air conditioning
refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes,
and process chemicals are typical compounds which are potentially
corrosive.
PRODUCTS OF THIS SORT SHOULD NOT BE STORED NEAR THE HEATER.
ALSO, AIR WHICH IS BROUGHT IN CONTACT WITH THE HEATER SHOULD
NOT CONTAIN ANY OF THESE CHEMICALS. IF NECESSARY,
UNCONTAMINATED AIR SHOULD BE OBTAINED FROM REMOTE OR OUTSIDE
SOURCES.
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED
TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES.
SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND
ASPHYXIATION.
Heater must be protected from freezing downdrafts during shutdown
periods.
NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO THE OUTDOORS
AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER
OPERATION, FIRE, EXPLOSION OR ASPHYXIATION.

VENT PIPE TERMINATION

NOTE: Before installing venting, determine place of vent pipe termination.
See Figure 6 before proceeding.
DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE EXHAUST OR
INTAKE WILL BE OBJECTIONABLE. THIS INCLUDES LOCATIONS CLOSE TO
OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE VENT
AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OR CEILINGS
UNLESS RUBBER ISOLATION PIPE HANGERS ARE USED. THIS PREVENTS
ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES.
The vent system must terminate so that proper clearances are maintained
as cited in local codes or the latest edition of the ANSI Z223.1/NFPA 54.
1. Do not terminate the exhaust vent terminal over public area where
condensate or vapor can cause nuisance or hazard.
2. For direct vent, the venting system shall terminate at least 1' (30.5 cm)
below, 1' (30.5 cm) horizontally from or 1' (30.5 cm) above any door,
window, or gravity air inlet into building.
6
WARNING

VENTING

WARNING
WARNING
CAUTION
IMPORTANT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents