8-4 WIRING CONNECTION METHOD
<<Caution for wiring>>
• The indoor units in the same system can be connected to the power supply from one branch switch. How-
ever, selection of branch switch, branch over current circuit breaker and wiring size must be according to
applicable legislation.
• For connection to the terminal block, use ring type crimp style terminals with insulation sleeve or treat the
wiring with insulation.
• If the above is not available, make sure to observe the following items.
• 2 wirings of different sizes to the terminal block for power supply is prohibited.
Connection of 2 wirings
of same size must be
carried out on both sides.
(Abnormal heating may occur if the wirings are not tightened securely.)
• Use the required wirings, connect them securely and fix these wirings so that external force may not apply
to the terminals.
• Use a proper screw driver for tightening the terminal screws. If an improper screw driver is used, it may
damage the screw head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged. Refer to the table shown below for tightening torque of
terminals.
Terminal block for remote controller and transmission wirings
Terminal block for power supply
Earth terminal
• Conduct wiring so that the earth lead comes out from the notched part of the cup washer. (Otherwise, earth
lead contact will be insufficient and grounding effect may be lost.)
• Do not carry out soldering finish when stranded wirings are used.
English
Insulation sleeve
Ring type crimp style terminals
Connection of 2 wirings
on one side is prohibited.
Ring type crimp style terminal
Connection of wirings of
different sizes is
prohibited.
Tightening torque (N·m)
0.88±0.08
1.47±0.14
1.69±0.25
Cup washer
Notched part
Wiring
18