Heater Placement Guidelines; Systems With 90° & 180° Elbows - Schwank S100 Installation & Owner's Manual

Schwank low intensity tube type infrared heaters
Hide thumbs Also See for S100:
Table of Contents

Advertisement

TABLE 2: GUIDELINES FOR HEATER PLACEMENT
MODEL
"Straight" or
"U-Tube"
S100 / ITB 200
S100 / ITB 175
S100 / ITB 155
S100 / ITB 130
S100 / ITB 110
S100 / ITB 100
S100 / ITB 80
S100 / ITB 60
S100 / ITB 45
*
RECOMMENDED MOUNTING HEIGHTS are typical to provide optimum comfort in general
space heating applications. Variance to these typical heights can occur in some applications:

Higher mounting heights due to structure or application requirements

Lower mounting heights for area or 'spot' heat, or in areas with greater infiltration losses
(near overhead doors, etc)
IMPORTANT: Single or multiple heater placement must be such that continu-
ous operation of heater(s) will not cause combustible material or materials in
storage to reach a temperature in excess of ambient temperature plus 90F°
(50C°).
It is the installer's responsibility to ensure that building materials with a
low heat tolerance which may degrade at lower temperatures are pro-
tected to prevent degradation. Examples of low heat tolerance materials
include vinyl siding, fabrics, some plastics, filmy materials, etc.
Refer to "Clearance to Combustibles" information on pages 6 to 8, and
Figure 1 and Table 1.
7.
SYSTEMS INCORPORATING 90° ELBOWS AND 180° ELBOWS
The radiant tube heater can be installed in configurations as illustrated in FIGURE 4. (below)
with a maximum of two 90° elbows per heater. The use of elbows reduces the total maximum
vent allowable. (See Section 11 : Flue venting)
S100-F / ITB-F I&O Manual
IM101230
RD: JAN 2014
RL: 9A
MAXIMUM
DISTANCE
MOUNTING
BETWEEN
HEIGHT
HEATERS
ft (m)
18 – 25 (6 - 8)
18 – 25 (6 - 8)
16 – 21 (5 - 7)
15 – 21 (5 - 7)
13 – 19 (4 - 6)
13 – 19 (4 - 6)
10 – 16 (3 - 5)
8 – 14 (2.5 - 5)
8 – 12 (2.5 - 4)
DISTANCE – OUTSIDE WALL
TO HEATER LONG AXIS
(PARALLEL TO WALL) IN "FEET"
HORIZONTAL
ft (m)
ft (m)
50 (15)
17 – 25 (5 - 8)
50 (15)
17 – 25 (5 - 8)
45 (14)
15 – 20 (5 - 7)
40 (12)
15 – 20 (5 - 7)
35 (11)
13 – 18 (4 - 6)
35 (11)
13 – 18 (4 - 6)
30 (9)
12 – 16 (4 - 5)
25 (8)
11 – 15 (3.4 - 5)
20 (6)
8 – 12 (2.5 - 4)
12
ANGLE
COMBUSTIBLE
CLEARANCE
BEHIND
(refer to Table 1)