2.2 INSTALLATION IN COMMERCIAL GARAGES

The Schwank Luminous Heaters are suitable for
use in commercial garages when installed in ac-
cordance with ANSI/NFPA No. 88B 1985 (latest
edition), which states clearances to combustible
construction or material in storage, from heater
and vent, must conform to standard NFPA No. 54
(ANSI Z223.1 latest edition), in

2.3 INSTALLATIONS OTHER THAN SPACE HEATING

Use for process applications will void the C.S.A.
certification and require governing authority field
certification at the installers / owners
responsibility and expense.

2.4 MOUNTING CLEARANCES

The Schwank Luminous Heater must be
mounted with minimum clearances as shown in
sections 8.3 to 8.5. It should also be located with
respect to building construction and
WARNING:
The Schwank Luminous Heaters cannot be installed inside degreas-
ing plants, nor can they be in an area where chlorine, fluorine or bro-
mine are present.

2.5 HEATER MOUNTING

The Schwank Luminous Heaters are approved for
both horizontal and angle mounting. When angle
mounting, the short axis may be rotated in either
direction to a maximum of 30
IMPORTANT:
For either horizontal or angle mounting, the long axis of the heater
must be level. Use only non-combustible mounting hardware.
0
degrees
Page 2
the U.S.A. and the CSA B149.1 in Canada.
"Overhead heaters shall be installed at least (8)
feet above the floor". In addition, they shall be lo-
cated high enough to maintain the minimum dis-
tance to combustibles, as shown on the heater rat-
ing plate, between the heater and any vehicles
parked below the heater
equipment so as to provide sufficient clearance
and accessibility for servicing and cleaning of
burners and ignition control.
with the venturi always in the upper position. Im-
proper angle mounting can result in damage to the
heater or unsafe operation.
SP-MECM-BX-05A
ecoSchwank - Millivolt Manual
RD: MAY, 2004
RL: 5
KH