Installing The Branch Joints - Samsung DVM PLUS III HR Installation Manual

Dvm plus iii hr rd***vrxf series
Hide thumbs Also See for DVM PLUS III HR:
Table of Contents

Advertisement

installing the unit
REFRIGERANT PIPING WORKS

Installing the branch joints

 Y-joint
• Install the Y-joint 'horizontally' or 'vertically'.
Note
Keep a minimum distance of 500mm(19-1/2") or more before
CAUTION
connecting a branch joint.
Pipe
To outdoor unit
Install the Y-joint within ±15° on
the horizontal or on the vertical.
26_ installing the unit
DVM PLUS3 HR_IM_E_32805-2.indd 26
Install horizontally
Install vertically
• When using A~J type of Y-joint, connect the Y-joint to the pipe with provided reducer.
• When using K~Z type of Y-joint, connect the Y-joint to the pipe by cutting the inlet of the
Y-joint or provided reducer properly.
Rear
Reducer
Reducer
Rear
Front
10~15mm(3/8~5/8")
or more
To other branch
joint or indoor unit
Pipe
Main pipe
500mm(19-1/2")
or more
2011-11-11 오후 4:18:24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents