INSULATING THE REFRIGERANT PIPE

Insulating the refrigerant

• You must check if there is a gas leak before completing all the installation process.
• Use EPDM insulation which meets the following condition.
Density
Dimension change route by heat
Water absorption rate
Thermal conductivity
Moisture transpiration factor
Moisture transpiration grade
Formaldehyde dispersion
Oxygen rate

Selecting the insulation of the refrigerant pipe

• Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.
• The standard condition is 30°C, less than humidity 85%. If the condition is in high humidity, use
one grade thicker.
Pipe
Liquid pipe
Gas pipe
Insulating the refrigerant pipe
• Be sure to insulate the refrigerant pipe, joints and connections with class 'o' material.
• If you insulate the pipes, the condensed water does not fall from the pipes and the capacity
of the air conditioner is improved.
• Check if there are any insulation cracks on the bent pipe.
Gas side pipe
38_ installing the unit
DVM PLUS3 HR_IM_E_32805-2.indd 38
Item
Pipe size (mm)
Ø6.35~Ø9.52
Ø12.70~Ø50.80
Ø6.35
Ø9.52
Ø12.70
Ø15.88
Ø19.05
Ø22.23
Ø25.40
Ø28.58
Ø31.75
Ø38.10
Ø44.45
Ø50.80
Clamp
Insulation
Indoor
unit
Liquid side pipe
Unit
3
g/cm
%
3
g/cm
kcal/m·h·˚C
ng/(m²·s·Pa)
g/(m²·24h)
mg/L
%
Insulator(Cooling, Heating)
Standard
High humidity
[30°C, 85%]
[30 °C, 85% or more]
EPDM, NBR
9t
13t
13t
19t
25t
19t
32t
25t
38t
Insulation
Indoor unit
Install the insulation
to be overlapped
Standard
0.048~0.096
-5 or less
0.005 or less
0.032 or less
15 or less
15 or less
-
25 or less
Remarks
Heat resisting
temperature is more
than 120°C