preparing the installation

INSTALLING THE DRAIN PIPE

• Insert the provided drain plug at the 2 sides of the bottom of the unit and then connect the drain pipe.
• Install the drain pipe at the rear side of the unit to get a sufficient space for repairs and service.
Outdoor unit
(Rear side)
When installing single outdoor unit
Outdoor unit
(Rear side)
Drain
plug
More than
1/50 slope
• Do not install a trap on the pipe.
And, install the drain pipe horizontally with a slope of 1/50 or more.
• Insulate the drain pipe and drain plug with insulation over 10t.
• Install heating device to the drain pipe to prevent it from being frozen.
Install the safety equipment for a heating appliance.
14_ preparing the installation
DVM PLUS3 HR_IM_E_32805-2.indd 14
Drain plug
When installing multiple outdoor units
Outdoor unit
(Rear side)
Open to air
Drain
plug
More than 1/50 slope
Drain pipe
Outdoor unit
Outdoor unit
(Rear side)
(Rear side)
Open to air