installing the unit
REFRIGERANT PIPING WORKS
 Outdoor joint
Installation of outdoor joint
Use the attached reducer properly according to the selected pipe size.
To other outdoor unit
To other outdoor unit
Note
To other outdoor unit
To the other outdoor joint
Note
28_ installing the unit
DVM PLUS3 HR_IM_E_32805-2.indd 28
High pressure gas pipe
Gas pipe
Liquid pipe
To other outdoor
joint or outdoor unit
Pipe
Reducer
Reducer at the
liquid side
Pipe
To other outdoor joint or
Y-joint of the main pipe
<Liquid pipe>
Pipe
To other outdoor
joint or outdoor unit
Reducer
Reducer
Pipe
To other outdoor joint or
Y- joint of the main pipe
<Gas pipe, High pressure gas pipe>
• When using A~J type of Outdoor joint, connect the Outdoor joint to the pipe with provided reducer.
• When using K~Z type of Outdoor joint, connect the Outdoor joint to the pipe by cutting
provided reducer properly.
Pipe
To the other
outdoor joint
Pipe
or outdoor unit
T-joint (Field supply)
or outdoor unit
<T-joint for oil balancing>
Keep in mind that T-joint must be installed horizontally to have best oil return to each
compressor.
Oil balancing
pipe
Do not install the outdoor
joint like the above diagram.
To other outdoor unit
 Install the oil balancing pipe without T-joint when
connecting 2 outdoor units.
<Oil balancing pipe>
To other outdoor
joint or outdoor unit
10~15mm(3/8-5/8") or more
Oil balancing pipe