Anchor Specifications - Samsung DVM PLUS III HR Installation Manual

Dvm plus iii hr rd***vrxf series
Hide thumbs Also See for DVM PLUS III HR:
Table of Contents

Advertisement

preparing the installation
INSTALLING THE OUTDOOR UNIT
Outdoor unit base mount and anchor bolt position
A
B
• When tightening the anchor bolt
- Tighten the rubber washer to prevent the outdoor unit bolt connection part from corroding.
CAUTION
• When connecting the pipes
- Check the strength of the roof to install the outdoor unit and make sure to have a waterproof
floor of the roof.
- Make sure that a proper drainage system has been put in place around the outdoor unit.
- To protect the internal components of the outdoor unit, secure the pipework entrance to the
unit.

Anchor specifications

m
a
INSTALLING DUCT FOR HORIZONTAL EXHAUST DISCHARGE
• It is necessary to install an air-discharge duct(field supply) to direct exhaust from the fan horizontally if it
is difficult to provide a minimum space of 2m(6'7") between the air-discharge duct outlet and a nearby
obstacle as shown in the figure.
Discharged air
12_ preparing the installation
DVM PLUS3 HR_IM_E_32805-2.indd 12
Model
A
B
Anchor bolt
Rubber washer
Close the
part.
(When the pipe is projected to the front side)
Liquid side pipe
Gas side pipe
Diameter of
Size
drill bit (a)
length (b)
M10
14mm(1/2")
Upper floor
Ex) Balcony
Unit:mm(inch)
RD075VRX
RD125VRX
RD100VRX
880(34-5/8)
1200(47-1/4)
738(29)
1058(41-5/8)
Anchor
Sleeve
length (c)
75mm(3")
40mm(1-1/2")
Suction air
Ex) Mechanical room
Insert
Fastening
depth
torque
50mm(2")
30N·m
Discharged air
Louver
2011-11-11 오후 4:18:12